Technical item or
function
Technical item or function Technical information
Control character-
istics
Switching frequency (see pa-
rameter P3.1.2.3)
200–500 V
MR4-MR6:
1.5–10 kHz
Default: 6 kHz (except for 0012 2, 0031 2, 0062 2, 0012 5, 0031 5 and
0061 5: 4 kHz)
MR7-MR9:
1.5–6 kHz
Default: MR7: 4 kHz, MR8: 3 kHz, MR9: 2 kHz
600–690 V
MR5-MR9:
1.5–6 kHz
Default: 2 kHz
For a product that is configured for a C4 installation on IT network the
maximum switching frequency is limited to default 2kHz.
Automatic switching frequency derating in case of overload.
Frequency reference:
Analog input
Panel reference
Resolution 0.1% (10-bit), accuracy ±1%
Resolution 0.01 Hz
Field weakening point 8–320 Hz
Acceleration time 0.1–3000 s
Deceleration time 0.1–3000 s
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711
134 | Danfoss A/S © 2019.05