Technical item or
function
Technical item or function Technical information
EMC (at default set-
tings)
Immunity Fulfils EN 61800-3 (2004), 1st and 2nd environment
Emissions 200–500 V: EN 61800-3 (2004), category C2.
All: The product is configurable to category C4 for installation on IT
networks. The drive can be modified for IT type mains. See 6.6 Installa-
tion in an IT System. The IP00/UL Open Type drive has by default cate-
gory C4.
Noise level Average noise level (min-max)
sound pressure level in dB(A)
The sound pressure depends on the cooling fan speed, which is con-
trolled in accordance with the drive temperature.
MR4: 45–56
MR5: 57–65
MR6: 63–72
MR7: 43–73
MR8: 58–73
MR9: 54–75
Safety standards
and certifications
- EN 61800-5-1 (2007), CE, cUL (See the nameplate of the drive for more
approvals.)
Protections Overvoltage trip limit Mains voltage 240 V: 456 VDC
Mains voltage 500 V: 911 VDC
Undervoltage trip limit Depends on mains voltage (0.8775 x mains voltage):
Mains voltage 240 V: trip limit 211 VDC
Mains voltage 400 V: trip limit 351 VDC
Mains voltage 500 V: trip limit 438 VDC
Mains voltage 525 V: trip limit 461 VDC
Earth fault protection Yes
Mains supervision Yes
Motor phase supervision Yes
Overcurrent protection Yes
Unit overtemperature protection Yes
Motor overload protection
Yes.
(1)
The motor overload protection activates at 110% of the full load
current.
Motor stall protection Yes
Motor underload protection Yes
Short-circuit protection of +24 V
and +10 V reference voltages
Yes
1
For the motor thermal memory and the memory retention function to obey the UL 61800-5-1 requirements, you must use the system software version FW0065V021 or a newer
version. If you use an older system software version, you must install a motor overtemperature protection to obey the UL regulations.
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711
144 | Danfoss A/S © 2019.05