C
D
F
C
B
A
e30bh227.10
E
A The grounding clamp for cable shield
C The grounding terminal
E The brake resistor cable
B The terminals
D The mains cable
F The motor cable
Illustration 13: Connecting the Stripped Cables
9. Make sure that the grounding conductor is connected to the motor and also to the terminals that are identified with the PE symbol.
A To comply with the requirements of the standard EN 61800-5-1, obey the instructions in 6.3 Grounding.
B If a double grounding is necessary, use the grounding terminal under the drive. Use an M5 screw and tighten it to 2.0 Nm or
17.7 lb-in.
e30bh228.10
= M5; 2 Nm
10. Attach again the cable cover.
Electrical Installation
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711| 47