A
C
B
e30bh281.10
7. Expose the shield of all 3 cables to make a 360° connection with the grounding clamp for cable shield.
e30bh282.10
8. Make sure that the grounding conductor is connected to the motor and also to the terminals that are identified with the PE symbol.
A To comply with the requirements of the standard EN 61800-5-1, obey the instructions in 6.3 Grounding.
B Connect the protective conductor to one of the screw connectors with a cable shoe and an M8 screw.
Electrical Installation
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711