EasyManua.ls Logo

Danfoss VLT AutomationDrive FC 301

Danfoss VLT AutomationDrive FC 301
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Start ( 18)
Freeze ref (27)
Speed up (29 )
Speed down (32 )
Speed
Reference
130BB840.11
Figure 6.1 Speed Up/Down
6.1.3
Start/Stop
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB802.10
Function Setting
5-10 Terminal 18
Digital Input
[8] Start*
5-12 Terminal 27
Digital Input
[0] No
operation
5-19 Terminal 37
Safe Stop
[1] Safe Stop
Alarm
* = Default Value
Notes/comments:
If 5-12 Terminal 27 Digital Input
is set to [0] No operation, a
jumper wire to terminal 27 is
not needed.
D IN 37 is an option.
Table 6.7 Start/Stop Command with Safe Stop Option
130BB805.11
Speed
Start (18)
Figure 6.2 Start/Stop Command with Safe Stop
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB803.10
Function Setting
5-10 Terminal 18
Digital Input
[9] Latched
Start
5-12 Terminal 27
Digital Input
[6] Stop
Inverse
* = Default Value
Notes/comments:
If 5-12 Terminal 27 Digital Input
is set to [0] No operation, a
jumper wire to terminal 27 is
not needed.
D IN 37 is an option.
Table 6.8 Pulse Start/Stop
Speed
130BB806.10
Latched Start (18)
Stop Inverse (27)
Figure 6.3 Latched Start/Stop Inverse
Application Set-up Examples Instruction Manual
34 Danfoss A/S © Rev. 09/2014 All rights reserved. MG33AP22
66

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Related product manuals