8.9 Power Ratings, Weight and Dimensions
Enclosure Type A1 A2 A3 A4 A5 B1 B2 B3 B4 C1 C2 C3 C4 D3h
Rated
Power
(hp [kW])
200–240 V 0.34–2
[0.25–
1.5]
0.34–3
[0.25–2.2]
4–5 [3–3.7]
0.34–3
[0.25–
2.2]
0.34–5
[0.25–
3.7]
7.5–10
[5.5–7.5]
15 [11]
7.5–10
[5.5–
7.5]
15–20
[11–15]
20–30
[15–22]
40–50
[30–37]
25–30
[18.5–
22]
40–50
[30–
37]
-
380–480/500 V 0.5–2
[0.37–
1.5]
0.5–5
[0.37–4.0]
7.5–10
[5.5–7.5]
0.5–5
[0.37–4]
0.5–10
[0.37–
7.5]
15–20
[11–15]
25–30
[18.5–22]
15–20
[11–15]
25–40
[18.5–
30]
40–60
[30–45]
75–100
[55–75]
50–60
[37-45]
75–100
[55–
75]
-
525–600 V
- -
1–10
[0.75–7.5]
-
1–10
[0.75–
7.5]
15–20
[11–15]
25–30
[18.5–22]
15–20
[11–15]
25–40
[18.5–
30]
40–60
[30–45]
75–125
[55–90]
50–60
[37-45]
75–125
[55–
90]
-
525–690 V
- -
1.5–10
[1.1-7.5]
- - -
15–30
[11–22]
-
15–40
[11–30]
-
40–100
[30–75]
50–60
[37-45]
50–60
[37-45]
75–
100
[55–
75]
IP
NEMA
20
Chas-
sis
20
Chas-
sis
21
Type 1
20
Chas-
sis
21
Type 1
55/66
Type
12/4X
55/66
Type
12/4X
21/55/66
Type
1/12/4X
21/55/66
Type
1/12/4X
20
Chas-
sis
20
Chas-
sis
21/55/66
Type
1/12/4X
21/55/66
Type
1/12/4X
20
Chas-
sis
20
Chas-
sis
20
Chas-
sis
Height (in [mm])
Height of backplate A*
7.87
[200]
10.55
[268]
14.76
[375]
10.55
[268]
14.76
[375]
15.35
[390]
16.54
[420]
18.9
[480]
25.59
[650]
15.71
[399]
20.47
[520]
26.77
[680]
30.32
[770]
21.65
[550]
25.98
[660]
35.79
[909]
Height with de-coupling
plate for serial communi-
cation bus cables
A
12.44
[316]
14.72
[374]
-
14.72
[374]
- - - - -
16.54
[420]
23.43
[595]
- -
24.8
[630]
31.5
[800]
-
Distance between
mounting holes
a
7.48
[190]
10.12
[257]
13.78
[350]
10.12
[257]
13.78
[350]
15.79
[401]
15.83
[402]
17.87
[454]
24.57
[624]
14.96
[380]
19.49
[495]
25.5 [648] 29.1 [739]
20.51
[521]
24.84
[631]
-
Width (in [mm])
Width of backplate B 2.95 [75]
3.54
[90]
3.54
[90]
5.12
[130]
5.12
[130]
7.87
[200]
9.53
[242]
9.53
[242]
9.53
[242]
6.5
[165]
9.06
[230]
12.13
[308]
14.57
[370]
12.13
[308]
14.57
[370]
9.84
[250]
Width of backplate with
1 C option
B -
5.12
[130]
5.12
[130]
6.73
[170]
6.73
[170]
-
9.53
[242]
9.53
[242]
9.53
[242]
8.07
[205]
9.06
[230]
12.13
[308]
14.57
[370]
12.13
[308]
14.57
[370]
-
Width of backplate with
two C options
B -
5.91
[150]
5.91
[150]
7.48
[190]
7.48
[190]
-
9.53
[242]
9.53
[242]
9.53
[242]
8.86
[225]
9.06
[230]
12.13
[308]
14.57
[370]
12.13
[308]
14.57
[370]
-
Distance between
mounting holes
b 2.36 [60]
2.76
[70]
2.76
[70]
4.33
[110]
4.33
[110]
6.73
[171]
8.47
[215]
8.27
[210]
8.27
[210]
5.51
[140]
7.87
[200]
10.71
[272]
13.15
[334]
10.63
[270]
13
[330]
-
Specifications Instruction Manual
MG33AP22 Danfoss A/S © Rev. 09/2014 All rights reserved. 77
8 8

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals