Enclosure Type A1 A2 A3 A4 A5 B1 B2 B3 B4 C1 C2 C3 C4 D3h
Rated
Power
(hp [kW])
200–240 V 0.34–2
[0.25–
1.5]
0.34–3
[0.25–2.2]
4–5 [3–3.7]
0.34–3
[0.25–
2.2]
0.34–5
[0.25–
3.7]
7.5–10
[5.5–7.5]
15 [11]
7.5–10
[5.5–7.5]
15–20
[11–15]
20–30
[15–22]
40–50
[30–37]
25–30
[18.5–
22]
40–50
[30–37]
-
380–480/500 V 0.5–2
[0.37–
1.5]
0.5–5
[0.37–4.0]
7.5–10
[5.5–7.5]
0.5–5
[0.37–4]
0.5–10
[0.37–
7.5]
15–20
[11–15]
25–30
[18.5–22]
15–20
[11–15]
25–40
[18.5–
30]
40–60
[30–45]
75–100
[55–75]
50–60
[37-45]
75–100
[55–75]
-
525–600 V
- -
1–10
[0.75–7.5]
-
1–10
[0.75–
7.5]
15–20
[11–15]
25–30
[18.5–22]
15–20
[11–15]
25–40
[18.5–
30]
40–60
[30–45]
75–125
[55–90]
50–60
[37-45]
75–125
[55–90]
-
525–690 V
- -
1.5–10 [1.1-7.5]
- - -
15–30
[11–22]
-
15–40
[11–30]
-
40–100
[30–75]
50–60
[37-45]
50–60
[37-45]
75–
100
[55–
75]
Depth (in [mm])
Depth without option A/B C
8.15
[207]
8.07
[205]
8.15
[207]
8.07
[205]
8.15
[207]
6.89
[175]
7.87
[200]
10.24
[260]
10.24
[260]
9.8 [249]
9.53
[242]
12.21
[310]
13.19
[335]
13.11
[333]
13.11
[333]
14.76
[375]
With option A/B C
8.47
[222]
8.66
[220]
8.47
[222]
8.66
[220]
8.47
[222]
6.89
[175]
7.87
[200]
10.24
[260]
10.24
[260]
10.32
[262]
9.53
[242]
12.21
[310]
13.19
[335]
13.11
[333]
13.11
[333]
14.76
[375]
Screw holes (in [mm])
c 0.24 [6.0]
0.315
[8.0]
0.315
[8.0]
0.315
[8.0]
0.315
[8.0]
0.33
[8.25]
0.33
[8.25]
0.47 [12] 0.47 [12] 0.315 [8] - 0.49 [12.5] 0.49 [12.5] - - -
d
ø0.32
[ø8]
ø0.43
[ø11]
ø0.43
[ø11]
ø0.43
[ø11]
ø0.43
[ø11]
ø0.47
[ø12]
ø0.47
[ø12]
ø0.75
[ø19]
ø0.75
[ø19]
0.47 [12] -
ø0.75
[ø19]
ø0.75
[ø19]
- - -
e ø0.2 [ø5]
ø0.22
[ø5.5]
ø0.22
[ø5.5]
ø0.22
[ø5.5]
ø0.22
[ø5.5]
ø0.26
[ø6.5]
ø0.26
[ø6.5]
ø0.35
[ø9]
ø0.35
[ø9]
0.27
[6.8]
0.34 [8.5] ø0.35 [ø9] ø0.35 [ø9]
0.34
[8.5]
0.34
[8.5]
-
f 0.2 [5]
0.35
[9]
0.35 [9]
0.26
[6.5]
0.26
[6.5]
0.24 [6] 0.35 [9] 0.35 [9] 0.35 [9]
0.31
[7.9]
0.59 [15] 0.39 [9.8] 0.39 [9.8]
0.67
[17]
0.67
[17]
Max weight (lbs [kg])
6 [2.7]
10.8
[4.9]
11.7
[5.3]
14.6
[6.6]
15.4
[7.0]
21.4 [9.7]
29.8/31.3
[13.5/14.
2]
50.7 [23] 59.5 [27] 26.5 [12]
51.8
[23.5]
99.3 [45] 143.3 [65]
77.2
[35]
110.3
[50]
136.7
[62]
Front cover tightening torque (in-lb [Nm])
Plastic cover (low IP) Click Click Click - - Click Click Click Click Click Click
17.7
[2.0]
17.7
[2.0]
-
Metal cover (IP55/66) - - -
13.28
[1.5]
13.28
[1.5]
19.47
[2.2]
19.47
[2.2]
- - 19.47 [2.2] 19.47 [2.2]
17.7
[2.0]
17.7
[2.0]
-
* See Figure 3.4 and Figure 3.5 for top and bottom mounting holes.
Table 8.25 Power Ratings, Weight and Dimensions
Specifications Instruction Manual
78 Danfoss A/S © Rev. 09/2014 All rights reserved. MG33AP22
88

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals