6.1.6 Motor Thermistor
WARNING
THERMISTOR INSULATION
Risk of personal injury or equipment damage.
•
Use only thermistors with reinforced or double
insulation to meet PELV insulation
requirements.
Parameters
130BB686.12
VLT
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
A53
U - I
D IN
37
Function Setting
1-90 Motor
Thermal
Protection
[2]
Thermistor
trip
1-93 Thermistor
Source
[1] Analog
input 53
* = Default Value
Notes/comments:
If only a warning is desired,
parameter 1-90 Motor Thermal
Protection should be set to
[1] Thermistor warning.
D IN 37 is an option.
Table 6.12 Motor Thermistor
6.1.7
SLC
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
R1R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
130BB839.10
Function Setting
4-30 Motor
Feedback Loss
Function
[1] Warning
4-31 Motor
Feedback Speed
Error
100 RPM
4-32 Motor
Feedback Loss
Timeout
5 s
7-00 Speed PID
Feedback Source
[2] MCB 102
17-11 Resolution
(PPR)
1024*
13-00 SL
Controller Mode
[1] On
13-01 Start Event [19] Warning
13-02 Stop Event [44] Reset
key
13-10 Comparator
Operand
[21] Warning
no.
13-11 Comparator
Operator
[1] ≈*
13-12 Comparator
Value
90
13-51 SL
Controller Event
[22]
Comparator
0
13-52 SL
Controller Action
[32] Set
digital out A
low
5-40 Function
Relay
[80] SL
digital
output A
*=Default Value
Application Set-up Examples Instruction Manual