9-63 Actual Baud Rate
Option: Function:
[7] 3000 kbit/s
[8] 6000 kbit/s
[9] 12000 kbit/s
[10] 31,25 kbit/s
[11] 45,45 kbit/s
[255] * No baudrate
found
9-64 Device Identication
Range: Function:
0* [0 - 0 ] Device identication parameter.
9-65 Prole Number
Range: Function:
0* [0 - 0 ] This parameter contains the prole
identication. Byte 1 contains the
prole number and byte 2 the
version number of the prole.
9-67 Control Word 1
Range: Function:
0* [0 - 65535 ] This parameter accepts the control
word from a master class 2 in the
same format as PCD 1.
9-68 Status Word 1
Range: Function:
0* [0 - 65535 ] This parameter delivers the status
word for a master class 2 in the
same format as PCD 2.
9-70 Programming Set-up
This parameter is unique for LCP and eldbus. See
parameter 0-11 Programming Set-up.
Option: Function:
Select the set-up to edit.
[0] Factory setup Uses default data. This option can
be used as a data source to return
the other set-ups to a known state.
[1] Set-up 1 Edits set-up 1.
[2] Set-up 2 Edits set-up 2.
[3] Set-up 3 Edits set-up 3.
[4] Set-up 4 Edits set-up 4.
[9] * Active Set-up Follows the active set-up selected
in parameter 0-10 Active Set-up.
9-71 Probus Save Data Values
Option: Function:
Parameter values changed via
PROFINET are not automatically
stored in the non-volatile memory.
Use this parameter to activate a
function that stores parameter
values in the EEPROM non-volatile
memory, so changed parameter
values are retained at power-down.
[0] * O Deactivate the non-volatile storage
function.
[1] Store all
setups
Store all parameter values for all
set-ups in the non-volatile memory.
When all parameter values have
been stored, the selection returns
to [0] O.
[2] Store all
setups
Store all parameter values for all
set-ups in the non-volatile memory.
When all parameter values have
been stored, the selection returns
to [0] O.
9-72 ProbusDriveReset
Option: Function:
[0] * No action
[1] Power-on
reset
Reset frequency converter upon
power-up, as for power cycle.
[2] Power-on
reset prep
Prepare for resetting frequency
converter upon power-up.
[3] Comm option
reset
Reset the PROFINET option only,
the PROFINET option goes through
a power-up sequence.
When reset, the frequency
converter disappears from the
eldbus, which may cause a
communication error from the
master.
9-75 DO Identication
Range: Function:
0* [0 - 65535 ] Provides information about the DO
(Drive Object).
9-80 Dened Parameters (1)
Array [116]
No LCP access
Read only
Range: Function:
0* [0 - 9999 ] This parameter shows a list of all
the dened frequency converter
parameters available for PROFINET.
Parameter Descriptions VLT® AutomationDrive FC 361
110 Danfoss A/S © 03/2019 All rights reserved. MG06J202