EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive FC 361

Danfoss VLT AutomationDrive FC 361 Programming Guide

Danfoss VLT AutomationDrive FC 361
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #111 background imageLoading...
Page #111 background image
9-27 Parameter Edit
Option: Function:
Parameters can be edited via
PROFIBUS, the standard RS485
interface, or the LCP.
[0] Disabled Disable editing via PROFIBUS.
[1] * Enabled Enable editing via PROFIBUS.
9-28 Process Control
Option: Function:
Process control (setting of control
word, speed reference, and process
data) is possible via either
PROFINET or standard eldbus, but
not both simultaneously. Local
control is always possible via the
LCP. Control via process control is
possible via either terminals or
eldbus depending on the settings
in parameter 8-50 Coasting Select to
parameter 8-58 Prodrive OFF3
Select.
[0] Disable Disable process control via
PROFINET and enable process
control via standard eldbus or
PROFINET IO supervisor.
[1] * Enable cyclic
master
Enable process control via IO
controller and disable process
control via standard eldbus or
PROFINET IO supervisor.
9-44 Fault Message Counter
Range: Function:
0* [0 - 65535 ] This parameter shows the number
of error events stored in
parameter 9-45 Fault Code and
parameter 9-47 Fault Number. The
maximum buer capacity is eight
error events. The buer and counter
are set to 0 upon reset or power-
up.
9-45 Fault Code
Range: Function:
0* [0 - 0 ] This buer contains the alarm word
for all alarms and warnings that
have occurred since last reset or
power-up. The maximum buer
capacity is 8 error events.
9-47 Fault Number
Range: Function:
0* [0 - 0 ] This buer contains the alarm
number (for example, 2 for live zero
error, 4 for mains phase loss) for all
alarms and warnings that have
occurred since last reset or power-
up. The maximum buer capacity is
8 error events.
9-52 Fault Situation Counter
Range: Function:
0* [0 - 1000 ] This parameter shows the number
of error events that have occurred
since last reset or power-up.
9-53 Probus Warning Word
Read only
Range: Function:
0* [0 - 65535 ] This parameter shows PROFINET
communication warnings.
Bit Condition when bit is active
0 Connection with IO controller is not OK.
1
Reserved for status of connection with second IO
controller.
2 Not used.
3 Clear data command received.
4 Actual value is not updated.
5 No link on both ports.
6 Not used.
7 Initializing of PROFINET is not OK.
8 Frequency converter is tripped.
9 Internal CAN error.
10 Wrong conguration data from IO controller.
11 Not used.
12 Internal error occurred.
13 Not congured.
14 Timeout active.
15 Warning 34 active.
Table 4.17 PROFINET Communication Warnings
This parameter shows the actual PROFIBUS baud rate. The
PROFIBUS master automatically sets the baud rate.
9-63 Actual Baud Rate
Option: Function:
[0] 9,6 kbit/s
[1] 19,2 kbit/s
[2] 93,75 kbit/s
[3] 187,5 kbit/s
[4] 500 kbit/s
[6] 1500 kbit/s
Parameter Descriptions Programming Guide
MG06J202 Danfoss A/S © 03/2019 All rights reserved. 109
4 4

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 361

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 361 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 361 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 361
CategoryDC Drives
LanguageEnglish

Related product manuals