13-40 Logic Rule Boolean 1
Option: Function:
[47] Up key
[
▲
] is pressed. Only available on the
graphical LCP.
[48] Down key
[
▼
] is pressed. Only available on the
graphical LCP.
[50] Comparator 4
[51] Comparator 5
[60] Logic rule 4
[61] Logic rule 5
[70] SL Time-out 3
[71] SL Time-out 4
[72] SL Time-out 5
[73] SL Time-out 6
[74] SL Time-out 7
[75] Start
command
given
[76] Digital input
x30/2
[77] Digital input
x30/3
[78] Digital input
x30/4
[83] Broken Belt
[102] Relay 1
[103] Relay 2
13-41 Logic Rule Operator 1
Array [6]
Option: Function:
Select the 1
st
logical operator to
use on the boolean inputs from
parameter 13-40 Logic Rule Boolean
1 and parameter 13-42 Logic Rule
Boolean 2.
Parameter numbers in square
brackets stand for the boolean
inputs of parameters in parameter
group 13-** Smart Logic Control.
[0] DISABLED Ignores:
•
Parameter 13-42 Logic Rule
Boolean 2.
•
Parameter 13-43 Logic Rule
Operator 2.
•
Parameter 13-44 Logic Rule
Boolean 3.
[1] AND Evaluates the expression [13-40]
AND [13-42].
[2] OR Evaluates the expression [13-40] OR
[13-42].
13-41 Logic Rule Operator 1
Array [6]
Option: Function:
[3] AND NOT Evaluates the expression [13-40]
AND NOT [13-42].
[4] OR NOT Evaluates the expression [13-40] OR
NOT [13-42].
[5] NOT AND Evaluates the expression NOT
[13-40] AND [13-42].
[6] NOT OR Evaluates the expression NOT
[13-40] OR [13-42].
[7] NOT AND NOT Evaluates the expression NOT
[13-40] AND NOT [13-42].
[8] NOT OR NOT Evaluates the expression NOT
[13-40] OR NOT [13-42].
13-42 Logic Rule Boolean 2
Option: Function:
[0] False
Select the 2
nd
boolean (true or
false) input for the selected logic
rule. See parameter 13-01 Start Event
and parameter 13-02 Stop Event for
more information.
[1] True
[2] Running
[3] In range
[4] On reference
[5] Torque limit
[6] Current Limit
[7] Out of current
range
[8] Below I low
[9] Above I high
[10] Out of speed
range
[11] Below speed
low
[12] Above speed
high
[13] Out of feedb.
range
[14] Below feedb.
low
[15] Above feedb.
high
[16] Thermal
warning
[17] Mains out of
range
[18] Reversing
[19] Warning
[20] Alarm (trip)
Parameter Descriptions VLT® AutomationDrive FC 361
122 Danfoss A/S © 03/2019 All rights reserved. MG06J202
44