0-14   Readout: Edit Set-ups / Channel
Range: Function:
0*   [-2147483648
- 2147483647]
View the setting of 
parameter 0-11 Edit Set-up for each
of the 4 dierent communication
channels. When the number is
shown as a hex number, as it is in
the LCP, each number represents 1
channel.
Numbers 1–4 represent a set-up
number; F means factory setting;
and A means active set-up. The
channels are, from right to left: LCP,
FC bus, USB, HPFB1-5.
Example: The number AAAAAA21h
means the following:
•
The frequency converter
received the setting set-up
2 via a eldbus channel.
This selection is reected
in parameter 0-11 Edit Set-
up.
•
A user selected set-up 1
via the LCP.
•
All other channels are
using the active set-up.
4.1.3 0-2* LCP Display
Dene the variables shown in the LCP.
NOTICE
For information on how to write display texts, refer to:
•
Parameter 0-37 Display Text 1.
•
Parameter 0-38 Display Text 2.
•
Parameter 0-39 Display Text 3.
0-20   Display Line 1.1 Small
Option: Function:
Select a variable for display in line
1, left position.
[0] None No display value selected.
[37] Display Text 1
[38] Display Text 2
[39] Display Text 3
[748] FCD Feed Forward
[953] Probus Warning
Word
[1500] Operating Hours
[1501] Running Hours
[1502] kWh Counter
[1580] Fan Running Hours
0-20   Display Line 1.1 Small
Option: Function:
[1600] Control Word Present control word.
[1601] Reference [Unit] Total reference (sum of digital/
analog/preset/bus/freeze reference/
catch up and slow down) in
selected unit.
[1602] Reference % Total reference (sum of digital/
analog/preset/bus/freeze reference/
catch up and slow down) in
percent.
[1603] Status Word Present status word.
[1605] Main Actual Value
[%]
Actual value as a percentage.
[1609] Custom Readout
[1610] Power [kW] Actual power consumed by the
motor in kW.
[1611] Power [hp] Actual power consumed by the
motor in hp.
[1612] Motor Voltage Voltage supplied to the motor.
[1613] Frequency Motor frequency, that is the output
frequency from the frequency
converter in Hz.
[1614] Motor current Phase current of the motor
measured as eective value.
[1615] Frequency [%] Motor frequency, that is the output
frequency from the frequency
converter in percent.
[1616] Torque [Nm] Actual motor torque in Nm.
[1617]
*
Speed [RPM] Speed in RPM (revolutions per
minute), that is the motor shaft
speed in closed loop.
[1618] Motor Thermal Thermal load on the motor,
calculated by the ETR function.
[1620] Motor Angle
[1621] Torque [%] High
Res.
[1622] Torque [%] Present motor load as a percentage
of the rated motor torque.
[1624] Calibrated Stator
Resistance
[1630] DC Link Voltage DC-link voltage in the frequency
converter.
[1631] System Temp.
[1632] Brake Energy /s Present brake power transferred to
an external brake resistor.
Stated as an instant value.
[1633] Brake Energy
Average
Brake power transferred to an
external brake resistor. The mean
power is calculated continuously
for the most recent 120 s.
[1634] Heatsink Temp. Present heat sink temperature of
the frequency converter. The
cutout limit is 95 ±5 °C
(203 ±9 °F); cutting back in occurs
at 70 ±5 °C (203 ±9 °F).
Parameter Descriptions Programming Guide
MG06J202 Danfoss A/S © 03/2019 All rights reserved. 27