6-11 Terminal 53 High Voltage
Range: Function:
10 V* [ par. 6-10 -
10 V]
Enter the high voltage value. This
analog input scaling value should
correspond to the high reference
feedback value set in
parameter 6-15 Terminal 53 High
Ref./Feedb. Value.
6-12 Terminal 53 Low Current
Range: Function:
0.14 mA* [ 0 - par. 6-13
mA]
Enter the low current value. This
reference signal should correspond
to the minimum reference value,
set in parameter 3-02 Minimum
Reference. Set the value to exceed 2
mA in order to activate the live
zero timeout function in
parameter 6-01 Live Zero Timeout
Function.
6-13 Terminal 53 High Current
Range: Function:
20 mA* [ par. 6-12 -
20 mA]
Enter the high current value
corresponding to the high
reference/feedback set in
parameter 6-15 Terminal 53 High
Ref./Feedb. Value.
6-14 Terminal 53 Low Ref./Feedb. Value
Range: Function:
0 Referen-
ceFeedback
Unit*
[-999999.999
- 999999.999
Reference-
FeedbackUnit]
Enter the analog input scaling value
that corresponds to the low
voltage/low current set in
parameter 6-10 Terminal 53 Low
Voltage and parameter 6-12 Terminal
53 Low Current.
6-15 Terminal 53 High Ref./Feedb. Value
Range: Function:
Size
related*
[-999999.999
- 999999.999
Reference-
FeedbackUnit]
Enter the analog input scaling value
that corresponds to the maximum
reference feedback value set in
parameter 6-11 Terminal 53 High
Voltage and parameter 6-13 Terminal
53 High Current.
6-16 Terminal 53 Filter Time Constant
Range: Function:
0.01 s* [0.01 - 10 s]
NOTICE
This parameter cannot be
adjusted while the motor is
running.
6-16 Terminal 53 Filter Time Constant
Range: Function:
Enter the lter time constant. This
constant is a rst-order digital low-
pass lter time for suppressing
electrical noise in terminal 53. A
high value improves dampening
but also increases the delay
through the lter.
4.7.3 6-2* Analog Input 2
Parameters for conguring the scaling and limits for analog
input 2 (terminal 54).
6-20 Terminal 54 Low Voltage
Range: Function:
0.07 V* [ 0 - par. 6-21
V]
Enter the low voltage value. This
analog input scaling value should
correspond to the minimum
reference value set in
parameter 3-02 Minimum Reference.
See also chapter 4.4 Parameters: 3-**
Reference/Ramps.
6-21 Terminal 54 High Voltage
Range: Function:
10 V* [ par. 6-20 -
10 V]
Enter the high voltage value. This
analog input scaling value should
correspond to the high reference
feedback value set in
parameter 6-25 Terminal 54 High
Ref./Feedb. Value.
6-22 Terminal 54 Low Current
Range: Function:
Size
related*
[ 0 - par. 6-23
mA]
Enter the low current value. This
reference signal should correspond
to the minimum reference value,
set in parameter 3-02 Minimum
Reference. Enter the value that
exceeds 2 mA to activate the live
zero timeout function in
parameter 6-01 Live Zero Timeout
Function.
6-23 Terminal 54 High Current
Range: Function:
20 mA* [ par. 6-22 -
20 mA]
Enter the high current value
corresponding to the high reference
feedback value set in
parameter 6-25 Terminal 54 High
Ref./Feedb. Value.
Parameter Descriptions VLT® AutomationDrive FC 361
82 Danfoss A/S © 03/2019 All rights reserved. MG06J202