EasyManuals Logo

Danfoss VLT CDS 303 User Manual

Danfoss VLT CDS 303
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #148 background imageLoading...
Page #148 background image
6.16.14 28-** Compressor Function
Par.
No. #
Parameter description Default value 4-set-up Change
during
operation
Conver-
sion index
Type
28-0* Short Cycle Protection
28-00 Short Cycle Protection [1] Enabled All set-ups TRUE - Uint8
28-01 Interval between Starts 300 s All set-ups TRUE 0 Uint16
28-02 Minimum Run Time 12 s All set-ups TRUE 0 Uint16
28-1* Oil Return Management
28-10 Oil Return Management ExpressionLimit All set-ups FALSE - Uint8
28-11 Low Speed Running Time 60 min All set-ups TRUE 70 Uint16
28-12 Fixed Boost Interval 24 h All set-ups TRUE 74 Uint8
28-13 Boost Duration 30 s All set-ups FALSE 0 Uint8
28-2* Discharge Temperature Monitor
28-20 Temperature Source [0] None All set-ups FALSE - Uint8
28-21 Temperature Unit [60] °C All set-ups FALSE - Uint8
28-24 Warning Level 130 N/A All set-ups FALSE 0 Uint16
28-25 Warning Action [1] Decrease cooling All set-ups FALSE - Uint8
28-26 Emergency Level 145 N/A All set-ups FALSE 0 Uint16
28-27 Discharge Temperature 0 DTM_ReadoutUnit All set-ups TRUE 0 Int32
28-3* Crankcase Heating
28-30 Crankcase Heating Control ExpressionLimit All set-ups TRUE - Uint8
28-31 Heating DC Current ExpressionLimit All set-ups TRUE 0 Uint8
28-32 Crankcase Heating Delay 5 s All set-ups TRUE 0 Uint16
28-4* Anti-reverse Protection at Stop
28-40 Reverse Protection Control [0] Disabled All set-ups TRUE - Uint8
28-41 DC Brake Current 90 % All set-ups TRUE 0 Uint16
28-42 DC Braking Time ExpressionLimit All set-ups TRUE -1 Uint16
28-43 DC Brake Cut In Speed [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
28-44 DC Brake Cut In Speed [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
28-5* Load Prole
28-50 Reset Load Prole [0] Do not reset All set-ups TRUE - Uint8
28-59 Load Prole Data 0 N/A All set-ups TRUE 0 Uint16
28-7* Day/Night Settings
28-74 Night Speed Drop [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
28-76 Night Speed Drop [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
Parameter Descriptions
VLT
®
Compressor Drives CDS 302/CDS 303
146 Danfoss A/S © Rev. 2013-07-03 All rights reserved. MG34M422
6