8-35 Minimum Response Delay
Range: Function:
10 ms* [ 1 - 10000
ms]
Specify the minimum delay time
between receiving a request and
transmitting a response. This is used for
overcoming modem turnaround delays.
8-36 Max Response Delay
Range: Function:
Size
related*
[ 11 -
10001 ms]
Specify the maximum permissible
delay time between transmitting a
request and receiving a response. If a
response from the frequency converter
is exceeding the time setting then it
will be discarded.
8-37 Max Inter-Char Delay
Range: Function:
Size
related*
[ 0.00 -
35.00 ms]
Specify the maximum permissible time
interval between receipt of two bytes. This
parameter activates time-out if
transmission is interrupted.
This parameter is active only when
parameter 8-30 Protocol is set to [1] FC MC
protocol.
6.9.4 8-5* Digital/Bus
Parameters for conguring the control word Digital/Bus
merging.
NOTICE!
These parameters are active only when
parameter 8-01 Control Site is set to [0] Digital and control
word.
8-50 Coasting Select
Option: Function:
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
[0] Digital
input
Activates Start command via a digital input.
[1] Bus Activates Start command via the serial communi-
cation port or eldbus option.
[2] Logic
AND
Activates Start command via the eldbus/serial
communication port, AND additionally via one of
the digital inputs.
[3] Logic OR Activates Start command via the eldbus/serial
communication port OR via one of the digital
inputs.
8-51 Quick Stop Select
Select control of the Quick Stop function via the terminals
(digital input) and/or via the bus.
Option: Function:
[0] Digital input
[1] Bus
[2] Logic AND
[3] Logic OR
8-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals
(digital input) and/or via the eldbus.
NOTICE!
Only selection [0] Digital input is available
when parameter 1-10 Motor Construction is
set to [1] PM non-salient SPM.
[0] Digital
input
Activates Start command via a digital input.
8-53 Start Select
Option: Function:
Select control of the frequency converter start
function via the terminals (digital input) and/or
via the eldbus.
[0] Digital
input
Activates Start command via a digital input.
[1] Bus Activates Start command via the serial communi-
cation port or eldbus option.
[2] Logic
AND
Activates Start command via the eldbus/serial
communication port, AND additionally via one of
the digital inputs.
[3] Logic OR Activates Start command via the eldbus/serial
communication port OR via one of the digital
inputs.
8-54 Reverse Select
Option: Function:
[0] Digital
input
Select control of the frequency converter reverse
function via the terminals (digital input) and/or
via the eldbus.
[1] Bus Activates the Reverse command via the serial
communication port or eldbus option.
[2] Logic AND Activates the Reverse command via the eldbus/
serial communication port, AND additionally via
one of the digital inputs.
[3] Logic OR Activates the Reverse command via the eldbus/
serial communication port OR via one of the
digital inputs.
Parameter Descriptions Operating Instructions
MG34M422 Danfoss A/S © Rev. 2013-07-03 All rights reserved. 83
6
6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CDS 303 and is the answer not in the manual?

Danfoss VLT CDS 303 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CDS 303
CategoryDC Drives
LanguageEnglish

Related product manuals