EasyManuals Logo

Danfoss VLT CDS 303 User Manual

Danfoss VLT CDS 303
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #96 background imageLoading...
Page #96 background image
13-16 RS-FF Operand R
Option: Function:
[100] RS Flipop 6
[101] RS Flipop 7
6.10.5 13-2* Timers
Use the result (TRUE or FALSE) from timers directly to
dene an event (see parameter 13-51 SL Controller Event), or
as boolean input in a logic rule (see parameter 13-40 Logic
Rule Boolean 1, parameter 13-42 Logic Rule Boolean 2 or
parameter 13-44 Logic Rule Boolean 3). A timer is only FALSE
when started by an action (i.e. [29] Start timer 1) until the
timer value entered in this parameter is elapsed. Then it
becomes TRUE again.
All parameters in this parameter group are array
parameters with index 0 to 2. Select index 0 to program
Timer 0, select index 1 to program Timer 1, and so on.
13-20 SL Controller Timer
Range: Function:
Size
related*
[ 0.000 -
0.000 ]
Enter the value to dene the duration of
the FALSE output from the programmed
timer. A timer is only FALSE if it is
started by an action (i.e. [29] Start timer
1) and until the given timer value has
elapsed.
6.10.6 13-4* Logic Rules
Combine up to 3 boolean inputs (TRUE/FALSE inputs) from
timers, comtors, digital inputs, status bits and events using
the logical operators AND, OR, and NOT. Select boolean
inputs for the calculation in parameter 13-40 Logic Rule
Boolean 1, parameter 13-42 Logic Rule Boolean 2 and
parameter 13-44 Logic Rule Boolean 3. Dene the operators
used to logically combine the selected inputs in
parameter 13-41 Logic Rule Operator 1 and
parameter 13-43 Logic Rule Operator 2.
. . .
. . .
. . .
. . .
Par. 13-43
Logic Rule Operator 2
Par. 13-41
Logic Rule Operator 1
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Par. 13-44
Logic Rule Boolean 3
130BB673.10
Figure 6.18 Logic Rules
Priority of calculation
The results of parameter 13-40 Logic Rule Boolean 1,
parameter 13-41 Logic Rule Operator 1 and
parameter 13-42 Logic Rule Boolean 2 are calculated rst.
The outcome (TRUE/FALSE) of this calculation is combined
with the settings of parameter 13-43 Logic Rule Operator 2
and parameter 13-44 Logic Rule Boolean 3, yielding the nal
result (TRUE/FALSE) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Option: Function:
[0] FALSE Select the rst boolean (TRUE or
FALSE) input for the selected logic
rule.
See parameter 13-01 Start Event
([0] - [61]) and
parameter 13-02 Stop Event ([70] -
[75]) for further description.
[1] TRUE
[2] Running
[3] In range
[4] On reference
[5] Torque limit
[6] Current Limit
[7] Out of current range
[8] Below I low
[9] Above I high
[10] Out of speed range
[11] Below speed low
[12] Above speed high
[13] Out of feedb. range
[14] Below feedb. low
[15] Above feedb. high
[16] Thermal warning
[17] Mains out of range
[18] Reverse
[19] Warning
[20] Alarm (trip)
[21] Alarm (trip lock)
[22] Comparator 0
[23] Comparator 1
[24] Comparator 2
[25] Comparator 3
[26] Logic rule 0
[27] Logic rule 1
[28] Logic rule 2
[29] Logic rule 3
[30] SL Timeout 0
[31] SL Timeout 1
[32] SL Timeout 2
[33] Digital input DI18
[34] Digital input DI19
Parameter Descriptions
VLT
®
Compressor Drives CDS 302/CDS 303
94 Danfoss A/S © Rev. 2013-07-03 All rights reserved. MG34M422
6
6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CDS 303 and is the answer not in the manual?

Danfoss VLT CDS 303 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CDS 303
CategoryDC Drives
LanguageEnglish

Related product manuals