dap4 Settings for Ultra Units
Number of Fans:
Fan K-Factor:
Minimum Flow:
Maximum Flow:
Set Point:
One (Default)
348 (Default)
2000 CFM (Default)
32000 CFM (Default)
15000 CFM (Default)
Fan Flow Tuning PID - This screen will display if Display Airflow is selected
Status:
Setpoint:
Integration Time:
Band Per Fan:
Deviation Time:
Current Demand:
00 CFM (Reading, not a setting)
15000 CFM
5S
666 CFM
1s
40%
Alarm Setting: Audio Mode:
Pwr-Up:
EVD Alm Shutdown:
Maint Due Msg:
Stdby Alms Active:
None (Default)
Auto, No Alarm (Default)
Yes (Default)
None (Default)
No (Default)
Alarm Settings: Comp Short Cycle:
Floor Water Alarm Action:
Reset Alarm Log:
Alarm Screen Contact:
Yes (Default)
Alarm Only (Default)
No (Default)
No Contact Message (Default)
Flow Alarms: No Water Flow Action:
Wtr Flow Alm Dly:
Air Flow Dly:
Alarm Only (Default)
5s (Default)
5s (Default)
Return Air Alarms: Firestat Setpoint:
Hi Temp Alarm:
Set Point:
Lo Temp Alarm:
Set Point:
150F (Default)
Yes (Default)
80F (Default)
Yes (Default)
60F (Default)
Opt Temp Alarms: Low Disch Temp Alm:
Shut Off Comps:
Set Point:
Yes (Default)
No (Default)
45.0F
Humidity Alarms: HI Humidity Alarm:
Set Point:
Lo Humidity Alarm:
Set Point:
Yes (Default)
60% (Default)
Yes (Default)
40% (Default)
Freeze Alarm: Freeze-Stat Alarm:
EEV Alarms: Shutdown Comps:
Hi Superheat Delay:
Yes (Default)
90s (Default)