DKM-411 User Manual Rev_01 Firmware V-1.0
K46D03-EN - 53 -
The program mode is used to adjust timers, operational limits and the configuration of the unit.
Although a free PC program is provided for programming, every parameter may be modified through the front
panel, regardless of the operating mode.
When modified, program parameters are automatically recorded into a non-erasable memory and take effect
immediately.
The program mode will not affect the operation of the unit. Thus programs may be modified anytime.
To enter the program mode, press together with and buttons for 5 seconds.
When the program mode is entered, below password entry screen will be displayed.
A 4 digit password must be entered using with , and buttons.
The , buttons modify the value of the current digit. The button steps to the
next digit.
The unit supports 3 password levels. The level_1 is designed for field adjustable parameters. The level_2
is designed for factory adjustable parameters. The level_3 is reserved. It allows recalibration of the unit.
The password level-1 is factory set to ‘1234’ and the password level-2 is factory set to ‘9876’.
If a wrong password is entered, the unit will still allow access to the program parameters, but in read-only
mode.
If password “0000” is entered, only EVENT LOG file will be available.
Passwords are not front panel adjustable.
19.1. ENTERING THE PROGRAMMING MODE
19. PROGRAMMING
Press 2
buttons
for 5
seconds