DKM-411 User Manual Rev_01 Firmware V-1.0
K46D03-EN - 59 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
LCD Backlight
%
3
100
100
The intensity of the LCD back light.
Language
-
0
1
0
0: English language selected.
1: Local language selected. This
language may be downloaded.
Intermittent Alarm Timer
-
0
255
1
0: continuous alarm (horn) output
1..255: intermittent alarm output period
in seconds
Alarm Relay Timer
sec
0
120
60
The period during which the ALARM
relay is active. If the period is set to 0,
the alarm output is constantly on.
Status Prompt Window
Enable
-
0
1
0
0: Status prompts disabled
1: Status prompts enabled
Modem Selection
-
0
1
0
0: not used
1: external GSM Datakom modem
SMS Enable
-
0
1
0
0: SMS messages disabled
1: SMS messages enabled
GPRS Connection
Enable
-
0
1
0
0: GPRS disabled
1: GPRS enabled
Web Refresh Rate
sec
0
240
5
The unit will refresh the web page with
this interval.
RS-485 Enable
-
0
1
1
0: RS-485 port disabled
1: RS-485 port enabled
Modbus Address
-
0
240
1
Modbus controller identity used in
Modbus communication.
RS-485 Baud Rate
bps
2400
115200
9600
This is the data rate of the RS-485
Modbus port.
Ethernet Enable
-
0
1
1
0: ethernet port disabled
1: ethernet port enabled
Real Time Clock Adjust
-
0
255
117
This parameter trims precisely the real
time clock circuit. Values from 0 to 63
speed up the clock with 0.25sec/day
steps. Values from 127 to 64 slow down
the clock with 0.25sec/day steps.
Periodic event time
min
1
65000
60
This parameter adjusts the period for
periodic event logging.
Intermittent Alarm Relay
Enable
-
0
1
0
0: steady alarm output
1: intermittent alarm output
SMS on Output Change
-
0
1
0
This parameter controls SMS sending
when any output has changed state. No
warnings generated.
0: no SMS on output change
1: SMS sent on output change
Alarm Event Log Enable
-
0
1
1
0: No event logging on alarm
1: Event logged on alarm condition
Warning Event Log
Enable
-
0
1
1
0: No event logging on warning
1: Event logged on warning condition