DKM-411 User Manual Rev_01 Firmware V-1.0
K46D03-EN - 60 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Output Event Log Enable
-
0
1
1
0: No event log on output change
1: Event logged on output change
Input Event Log Enable
-
0
1
1
0: No event logging on intput change
1: Event logged on intput change
Power-on Event Log
Enable
-
0
1
1
0: No event logging at power-on
1: Event logged on power-on
Periodic Event Log
Enable
-
0
1
1
0: No periodicevent logging
1: Event logged periodically
Pprogramming Event Log
Enable
-
0
1
0
0: No event logging at program mode
entrance
1: Event logged on program mode
entrance
SMS on IP Change
-
0
1
0
0: no SMS on IP address change
1: SMS sent on IP addresschange
E-mail on IP Change
-
0
1
0
0: no e-mail on IP change
1: e-mail sent on IP change
SMS Commands
Enabled
-
0
1
0
0: SMS commands not accepted
1: SMS commands are accepted but
from listed telephone numbers only.
Ping Period
sec
30
900
120
The unit will check the availability of the
internet connection with this interval.
Rainbow Scada Refresh
Rate
sec
0
65535
60
The unit will update the distant
monitoring terminal with this rate.
Rainbow Scada
Address-1 Port
-
0
65535
90
This is the port number of the first
monitoring terminal address.
Rainbow Scada
Address-2 Port
-
0
65535
90
This is the port number of the second
monitoring terminal address.
Web Server Port
-
0
65535
80
This is the port number of the internal
web server. The unit will answer queries
to this port only.
Modbus TCP/IP Port
-
0
65535
502
Internal Modbus TCP/IP server’s port
number. The unit answers Modbus
requests to this port only.
SMTP Port
-
0
65535
587
Port number used for e-mail sending.
Log Record Period
sec
10
3600
60
This parameter adjusts the data logging
frequency to USB Flash memories.
Frequent recording will require more
memory capacity.
With a period of 60 seconds, 263MB is
consumed per year.
LCD Backlight Delay
min
0
1440
60
If no button is pressed during that
period, then the unit will reduce the LCD
screen backlight intensity in for
economy.
Flashing Relay ON Timer
min
0
1200
0
Flashing relay ON state duration timer.
Flashing Relay OFF
Timer
min
0
1200
0
Flashing relay OFF state duration.
20.1. CONTROLLER CONFIGURATION GROUP (continued)