4.1.29 Slot #8, 4 relay outputs (option M14.8)
Term. Function Technical data Description
126 NE/ND Relay 126
250 V AC/5 A
Configurable
127 Com.
128 NE/ND Relay 128
250 V AC/5 A
Configurable
129 Com.
130 NE/ND Relay 130
250 V AC/5 A
Configurable
131 Com.
132 NE/ND Relay 132
250 V AC/5 A
Configurable
133 Com.
4.1.30 Slot #8, external I/O module (option H8.8)
Term. Function Description
126 Not used CAN bus card option H8.8
127 Not used
128 CAN-L
129 GND
130 CAN-H
131 CAN-L
132 GND
133 CAN-H
Terminals 133 and 130 are internally connected. Terminals 131 and 128 are internally connec-
ted.