Use shielded twisted cable.
End resistor R = 120 Ohm.
The terminating resistor at the engine side might not be needed, refer to the engine manufac-
turers literature.
5.3.5 Cummins GCS (option H6)
Multi-line 2, option H6
DATA - B
131 132 133
DATA (GND)
DATA + A
Engine controller,
connector 06
DATA - B
18 20 31
DATA (GND)
DATA + A
Use shielded twisted cable.
The RS-485 Modbus lines need end resistors (end terminators) when the bus length exceeds 30
m. However, that is not the case here, as this communication line never exceeds 30 m.
Cable: Belden 3105A or equivalent. 22 AWG (0.6 mm
2
) twisted pair, shielded, <40 mΏ/m, min.
95 % shield coverage.