5.3 Communication
5.3.1 CAN bus (option G4/G5/G8)
Examples with three AGC units connected, for example one AGC mains and two generator AGC units.
It is not possible to mix CAN bus interface A and B.
Multi-line 2
CANbus interface A
A1 A2 A3
H GND L
Multi-line 2
CANbus interface A
A1 A2 A3
H GND L
Multi-line 2
CANbus interface A
A1 A2 A3
H GND L
120 120
Multi-line 2
CANbus interface B
B1 B2 B3
H GND L
Multi-line 2
CANbus interface B
B1 B2 B3
H GND L
Multi-line 2
CANbus interface B
B1 B2 B3
H GND L
120 120
Use shielded twisted cable.
End resistor R = 120 Ohm.
AGC-3 installation instructions 4189340728
UK
Wirings
DEIF A/S Page 55 of 65