5.3.3 Profibus DP (option H3)
Connection with 2-wire screened cable:
Multi-line 2
DATA + (B)
29 30 31
COM
DATA - (A)
Multi-line 2
DATA + (B)
29 30 31
COM
DATA - (A)
Standard Profibus DP
Active termination
(not provided by Deif)
DATA + (B)
Shield
DATA - (A)
DATA - (A)
Standard Profibus DP plug
(not provided by Deif)
Shield
DATA + (B)
PLC or other master device
The switch must be on the ON position
Use the IN side, not the OUT side
Use shielded twisted cable.
5.3.4 CAN bus engine communication (option H5)
Connection with 2-wire screened cable:
Multi-line 2
CAN-H
133 132 131
CAN-GND
CAN-L
CAN-L
ECM
engine control module
CAN-GND
CAN-H
120
120
AGC-3 installation instructions 4189340728