Connect PWM - to the engine battery negative and PWM + to the engine control system S-SPD
(speed) input (called RATED SPEED on the ADEM controller and PRIMARY THROTTLE on the
PEEC controller).
AVR control requires the D1 option.
4.1.16 Slot #4, analogue outputs for GOV/AVR or transducer (option E2)
Term. Function Description
65 Not used
66 0(4) to 20 mA Configurable
67 0
68 Not used
69 Not used
70 0(4) to 20 mA Configurable
71 0
72 Not used
4.1.17 Slot #5, AC measuring
Term. Function Technical data Description
73 I L1, s1 Generator current L1 x/1 A or x/5 A input
74 I L1, s2
75 I L2, s1 Generator current L2 x/1 A or x/5 A input
76 I L2, s2
77 I L3, s1 Generator current L3 x/1 A or x/5 A input
78 I L3, s2
79 U L1 Generator voltage L1 Max. 690 V AC phase-phase value
80 Not used
81 U L2 Generator voltage L2 Max. 690 V AC phase-phase value
82 Not used
83 U L3 Generator voltage L3 Max. 690 V AC phase-phase value
84 U
NEUTRAL
Generator voltage neutral
85 U L1 Mains/bus voltage L1 Max. 690 V AC phase-phase value
86 Not used
87 U L2 Mains/bus voltage L2 Max. 690 V AC phase-phase value
88 U
NEUTRAL
Mains/bus voltage neutral
89 U L3 Mains/bus voltage L3 Max. 690 V AC phase-phase value
AGC-3 installation instructions 4189340728
UK
Hardware
DEIF A/S Page 31 of 65