ASDA-A2  Chapter 8  Parameters 
Revision February, 2017    8-115 
 
Unit: 
- 
 
Range: 
0 ~ 2 
 
Data Size: 
16-bit 
 
Format: 
Decimal 
 
Settings: 
0: The value of P2-43, P2-44 and P2-45, P2-46 will retain. 
1: The value of P2-43, P2-44 and P2-45, P2-46 will retain after 
resonance suppression. 
2: Continuous resonance suppression 
Description of Auto Mode Setting: 
When it is set to 1: Auto resonance, the value returns to 0 
automatically and saves the point of resonance 
suppression when it is stable. If it is unstable, re-
power on or set back to 1 for re-estimation again. 
When it is set to 2: Continuous suppression automatically. When it is 
stable, the point of resonance suppression will be 
saved. If it is unstable, re-power on for re-
estimation. 
When switching to mode 0 from mode 2 or 1, the setting of P2-43, P2-
44, P2-45 and P2-46 will be saved automatically. 
P2-48    ANCL  Resonance Suppression Detection Level 
Address: 0260H 
0261H 
 
Operational 
Interface: 
Panel / Software  Communication 
Related Section: - 
 
Default: 
100 
 
Control 
Mode: 
ALL 
 
Unit: 
- 
 
Range: 
1 ~ 300% 
 
Data Size: 
16-bit 
 
Format: 
Decimal 
 
Settings: 
(The smaller the setting value is, the more sensitive the resonance will 
be.) 
P2-48↑, resonance sensitiveness↓ 
P2-48↓, resonance sensitiveness↑