ASDA-A2 Chapter 12 Absolute System
12-22 Revision February, 2017
. If there doesn’t have any error occurred during communication course for the host controller to
finish bit 0 to bit 79 (80 bits data), the functions of DI4, DO2, DO3 will be changed back to their
original functions before communication cycle started.
NOTE
If ABSW does not go back to high level signal after the changing of ABSE for signal low to high
that is a sign of error occurring, there must be some other errors existing. Please check if the
coordinate data still there, the voltage level of battery, or overflowing on the coordinate value.
A new communication cycle can be started only all of these errors been removed.

Table of Contents

Other manuals for Delta ASDA-A2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ASDA-A2 Series and is the answer not in the manual?

Delta ASDA-A2 Series Specifications

General IconGeneral
Enclosure RatingIP20
Control ModePosition, Speed, Torque
Communication InterfaceRS-485, CANopen
ProtectionOvercurrent, Overvoltage, Undervoltage, Overload, Overtemperature, Encoder error
Operating Temperature0°C to 55°C
Storage Temperature-20°C to 65°C
Humidity20% to 90% RH (non-condensing)
Altitude1000m max
Cooling MethodNatural cooling or forced air cooling
Encoder Feedback20-bit incremental encoder (standard), 17-bit absolute encoder (optional)