EasyManua.ls Logo

Delta ASDA-B2-F Series - Page 174

Delta ASDA-B2-F Series
291 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ASDA-B2-F Parameters
September, 2015 7-57
7
Read parameters: shows the DI status after combination
Write parameters: writes the software SDI status (The function of this parameter is the same
whether it is written via panel or communication.)
Example: The value of reading P4-07 is 0x0011, which means DI1 and DI5 are ON; the value of
writing P4-07 is 0x0011, which means software SDI1 and SDI5 are ON
Please refer to P2-10 ~ P2-14 for function program of digital input pin DI (DI1~DI5).
P4-08
PKEY Input Status of the Drive Keypad (Read-only)
A
ddress: 0410H
0411H
Operational
Interface:
Panel / Software Communication
Related
Section:
-
Default: -
Control
Mode:
ALL
Unit: - Range: (Read-only)
Format: HEX Data Size: 16-bit
Settings:
The aim is to check if the five keys MODE, UP, DOWN, SHIFT and SET can work normally.
P4-09
PKEY Digital Output Status (Read-only)
A
ddress: 0412H
0413H
Operational
Interface:
Panel / Software Communication
Related
Section:
4.4.5
Default: -
Control
Mode:
ALL
Unit: - Range: 0 ~ 0x1F
Format: HEX Data Size: 16-bit
Settings:
There is no difference between reading via panel or communication.
P4-10 CEN Adjustment Selection
A
ddress: 0414H
0415H
Operational
Interface:
Panel / Software Communication
Related
Section:
-
Default: 0
Control
Mode:
ALL
Unit: - Range: 0 ~ 6
Format: DEC Data Size: 16-bit
Settings:
0: Reserved
4: Execute the adjustment of current detector (W
phase) hardware offset
1: Reserved
5: Execute the adjustment of 1 ~ 4 hardware
offset
2: Reserved 6: Execute the adjustment of IGBT ADC
3: Execute the adjustment of current detector (V
phase) hardware offset
-
Note:
The adjustment function needs to be enabled by the setting of parameter P2-08. When adjusting, the external
wiring which connects to torque needs to be removed completely and must be in Servo Off status.
P4-11~P4-14 Reserved
P4-15 COF1 Current Detector (V1 Phase) Offset Adjustment
A
ddress: 041EH
041FH
Operational
Interface:
Panel / Software Communication
Related
Section:
-
Default: Factory default
Control
Mode:
ALL
Unit: - Range: 0 ~ 32767
Format: DEC Data Size: 16-bit
Settings:
Manually adjust the hardware offset. The adjustment function needs to be enabled by the setting of
parameter P2-08. It is not suggested to adjust the auxiliary adjustment. This parameter cannot be
reset.

Table of Contents

Related product manuals