Chapter 8 Option CardsC2000
8-43
8-16-5 To set the communication parameters when C2000 connects with PROFINET
When you operate VFD-C2000 through CMC-PN01, you should set the communication card as
the source of VFD-C2000 controls and settings. You need to use the keypad to configure the
following parameter addresses to the corresponding values:
8-16-6 LED indicator introduction
Name Indicator status Indication
Ready out indicator Yellow LED
Always on PN Stack starts normally
Flashing
PN Stack starts normally, and waiting
for syncing with MCU
Off PN Stack failed to start
MT out indicator Green LED - -
SD indicator Red LED - -
BF out indicator Red LED
Always on
Connection with PROFINET Controller
is interrupted
Flashing
Connection is in normal state, but the
communication with PROFINET
Controller is abnormally
Off
Connection with PROFINET Controller
is in normal state
ACT PHY1
indicator
Orange LED
Always on
It’s online, and exchanging the data
with Master normally
Flashing
It’s offline, but hand shaking the data
with Master
Off Initial state
LINK PHY1
indicator
Green LED
Always on Internet connection is in normal state
Off Doesn’t connect to network
ACT PHY2
indicator
Orange LED
Always on
It’s online, and exchanging the data
with Master normally
Flashing
It’s offline, but hand shaking the data
with Master
Off Initial state
LINK PHY2
indicator
Green LED
Always on Internet connection is in normal state
Off Doesn’t connect to network
Parameters Setting value Description
Pr.00-20 8
The frequency command is controlled by communication card
Pr.00-21 5
The frequency command is controlled by communication card
Pr.09-30 1
Use decoding method (60xx or 20xx)
Pr.09-60 12
Communication card identification:
When CMC-PN01 communication card is connected, the value
of this parameter displays “12”.