Chapter 9 Specification C2000
9-3
9-2 460V Series
Frame Size A B C
Model VFD-_ _ _ C_ _
007 015 022 037 040 055 075 110 150 185 220 300
*Output Rating
Normal Duty
Rated Output Capacity [kVA] 2.4 3.2 4.8 7.2 8.4 10 14 19 25 30 36 48
Rated Output Current [A] 3.0 4.0 6.0 9.0 10.5 12 18 24 32 38 45 60
Applicable Motor Output [kW] 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15 18.5 22 30
Applicable Motor Output [HP] 1 2 3 5 5 7.5 10 15 20 25 30 40
Overload Capacity
120% of rated output current: 1 minute for every 5 minutes;
160% of rated output current: 3 seconds for every 30 seconds
Max. Output Frequency [Hz] 0.00~599.00
Carrier Frequency [kHz] 2~15 (Default: 8) 2~10 (Default: 6)
Heavy Duty
Rated Output Capacity [kVA] 2.3 3.0 4.5 6.5 7.6 9.6 14 18 24 29 34 45
Rated Output Current [A] 2.9 3.8 5.7 8.1 9.5 11 17 23 30 36 43 57
Applicable Motor Output [kW] 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15 18.5 22
Applicable Motor Output [HP] 0.5 1 2 3 5 5 7.5 10 15 20 25 30
Overload Capacity
150% of rated output current: 1 minute for every 5 minutes;
180% of rated output current: 3 seconds for every 30 seconds
Max. Output Frequency [Hz] 0.00~300.00
Carrier Frequency [kHz] 2~15 (Default: 2) 2~10 (Default: 2)
Input Rating
Input Current [A]
Normal Duty 4.3 5.9 8.7 14 15.5 17 20 26 35 40 47 63
Heavy Duty 4.1 5.6 8.3 13 14.5 16 19 25 33 38 45 60
Rated Voltage / Frequency 3-phase AC 380V~480V ( -15%~+10%), 50 / 60Hz
Operating Voltage Range 323~528V
AC
Frequency Tolerance 47~63Hz
Efficiency [%] 97.8
Power Factor >0.98
Drive Weight [Kg] 2.6± 0.3 5.4± 1 9.8± 1.5
Cooling Method Natural cooling Fan cooling
Braking Chopper Frame A~C: Built-in
DC choke Frame A~C: Optional
EMC Filter VFDXXXC43A: Optional; Frame A~C VFDXXXC43E: Built-in
EMC-COP01 VFDXXXC43A: Optional; VFDXXXC43E: Built-in
Table 9-2
NOTE
1. * : The factory setting is Normal Duty mode.
2. The carrier frequency is default. Increasing the carrier frequency requires a reduction in current. Please refer to Chapter 9-7
Derating Curve of Ambient Temperature.
3. The AC motor drive should operate in derating current when its control method is set to FOC Sensorless, TQC+PG, TQC
sensorless. PM+PG, PM sensorless Please refer to Pr. 06-55 for more information.
4. Select the AC motor drive with capacity one grade larger for the impact load application.
5. The rated input current will be affected by not only Power Transformer and the connection of the reactors on input side, but
also fluctuates with the impedance of power side.
6. For Frame A, B and C, Model VFDXXXC43A is under IP20/NEMA1/UL TYPE1 protection level.
7. For Frame D and above, if the last character of the model is A then it is under IP20 protection level but the wiring terminal is
under IP00 protection level; if the last character of the model is E, it is under IP20/NEMA1/UL TYPE1 protection level.

Table of Contents

Other manuals for Delta C2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Series and is the answer not in the manual?

Delta C2000 Series Specifications

General IconGeneral
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Overload Capacity150% of rated current for 60 seconds
CommunicationDeviceNet
ProtectionOvervoltage, Undervoltage, Overcurrent, Overload, Overheat
Humidity5% to 95% (non-condensing)
CoolingForced air cooling
Control ModeV/F Control, Sensorless Vector Control