Chapter 9 Specification C2000
9-4
Frame Size D0 D E F G H
Model VFD-_ _ _ C_ _
370 450 550 750 900 1100 1320 1600 1850 2200 2800 3150 3550 4500
*Output Rating
Normal Duty
Rated Output Capacity [kVA] 58 73 88 120 143 175 207 247 295 367 438 491 544 720
Rated Output Current [A] 73 91 110 150 180 220 260 310 370 460 550 616 683 866
Applicable Motor Output [kW] 37 45 55 75 90 110 132 160 185 220 280 315 355 450
Applicable Motor Output [HP] 50 60 75 100 125 150 175 215 250 300 375 420 475 600
Overload Capacity
120% of rated output current: 1 minute for every 5 minutes;
160% of rated output current: 3 seconds for every 30 seconds
Max. Output Frequency [Hz] 0.00~599.00
Carrier Frequency [kHz] 2~10 (Default: 6) 2~9 (Default: 4)
Heavy Duty
Rated Output Capacity [kVA] 55 69 84 114 136 167 197 235 280 348 417 466 517 677
Rated Output Current [A] 69 86 105 143 171 209 247 295 352 437 523 585 649 815
Applicable Motor Output [kW] 30 37 45 55 75 90 110 132 160 185 220 280 315 355
Applicable Motor Output [HP] 40 53 60 75 100 125 150 175 215 250 300 375 425 475
Overload Capacity
150% of rated output current: 1 minute for every 5 minutes;
180% of rated output current: 3 seconds for every 30 seconds
Max. Output Frequency [Hz] 0.00~300.00
Carrier Frequency [kHz] 2~10 (Default: 2) 2~9 (Default: 2)
Input Rating
Input Current [A]
Normal Duty 74 101 114 157 167 207 240 300 380 400 494 555 625 866
Heavy Duty 70 96 108 149 159 197 228 285 361 380 469 527 594 815
Rated Voltage / Frequency 3-phase AC 380V~480V (-15% +10%), 50 / 60Hz
Operating Voltage Range 323~528V
AC
Frequency Tolerance 47~63Hz
Efficiency [%] 97.8 98.2
Power Factor >0.98
Drive Weight [Kg] 27 ± 1.5 38.5 ± 1.5 64.8 ± 1.5 86.5 ± 1.5 134 ± 4 228
Cooling Method Fan cooling
Braking Chopper Frame D0~H: Optional
DC choke Frame D0~H: Built-in
EMC Filter Frame D0~H: Optional
EMC-COP01 VFDXXXC43A:Optional; VFDXXXC43E: Built-in
Table 9-3
NOTE
1. * : The factory setting is Normal Duty mode.
2. The carrier frequency is default. Increasing the carrier frequency requires a reduction in current. Please refer to Chapter 9-7
Derating Curve of Ambient Temperature.
3. The AC motor drive should operate in derating current when its control method is set to FOC Sensorless, TQC+PG, TQC
sensorless. PM+PG, PM sensorless Please refer to Pr. 06-55 for more information.
4. Select the AC motor drive with capacity one grade larger for the impact load application.
5. The rated input current will be affected by not only Power Transformer and the connection of the reactors on input side, but
also fluctuates with the impedance of power side.
6. For Frame A, B and C, Model VFDXXXC43A is under IP20/NEMA1/UL TYPE1 protection level.
7. For Frame D and above, if the last character of the model is A then it is under IP20 protection level but the wiring terminal is
under IP00 protection level; if the last character of the model is E, it is under IP20/NEMA1/UL TYPE1 protection level.
8. Model VFD4500C43x does not have UL certification.