Chapter 9 Specification C2000
9-7
Frame Size F G H
Model VFD-_ _ _ C63B-00/21 1600 2000 2500 3150 4000 4500 5600 6300
*Output Rating
Light Duty
Rated Output Capacity [kVA] 215 263 347 418 494.5 534.7 678.5 776
Applicable Motor Output [690V, kW] 160 200 250 315 400 450 560 630
Applicable Motor Output [690V, HP] 215 270 335 425 530 600 745 850
Applicable Motor Output [575V, HP] 175 200 250 350 400 450 500 745
Rated Output Current [A] 180 220 290 350 430 465 590 675
Normal Duty
Rated Output Capacity [kVA] 179 215 239 347 402.5 442.7 534.7 776
Applicable Motor Output [690V, kW] 132 160 200 250 315 355 450 630
Applicable Motor Output [690V, HP] 175 215 270 335 425 475 600 850
Applicable Motor Output [575V, HP] 150 175 200 250 350 400 450 745
Rated Output Current [A] 150 180 220 290 350 385 465 675
Heavy Duty
Rated Output Capacity [kVA] 149 179 215 263 333.5 356.5 483 776
Applicable Motor Output [690V, kW] 110 132 160 200 250 280 400 630
Applicable Motor Output [690V, HP] 150 175 215 270 335 375 530 850
Applicable Motor Output [575V, HP] 125 150 175 200 250 335 450 745
Rated Output Current [A] 125 150 180 220 290 310 420 675
Carrier Frequency [kHz] 2~9 (Default: 4) 2~9 (Default: 3)
Input Rating
Input Current [A]
Light Duty 178 217 292 353 454 469 595 681
Normal Duty 148 178 222 292 353 388 504 681
Heavy Duty 123 148 181 222 292 313 423 681
Rated Voltage / Frequency 3-phase AC 525 V~ 690V ( -15%~+10%), 50/60 Hz
Operating Voltage Range 446 ~ 759 V
AC
Frequency Tolerance 47~63 Hz
Efficiency [%] 97 98
Power Factor >0.98
Drive Weight [Kg] 88 ± 1.5 135 ± 4 243 ± 5
Cooling Method Fan cooling
Braking Chopper Frame F~H: Optional
DC choke Frame F~H: Built-in
EMC Filter Frame F~H: Optional
Table 9-6
NOTE
* Parameter 00-16; available load modes: Light Duty (LD), Normal Duty (ND) and Heavy Duty (HD); default setting is LD mode