Chapter 9 Specification C2000
9-6
9-4 690V Series
Frame Size C D E
Model VFD-_ _ _ C63B-00 / -21 185 220 300 370 450 550 750 900 1100 1320
*Output Rating
Light Duty
Rated Output Capacity [kVA] 29 36 43 54 65 80 103 124 149 179
Applicable Motor Output [690V, kW] 18.5 22 30 37 45 55 75 90 110 132
Applicable Motor Output [690V, HP] 25 30 40 50 60 75 100 125 150 175
Applicable Motor Output [575V, HP] 20 25 30 40 50 60 75 100 125 150
Rated Output Current [A] 24 30 36 45 54 67 86 104 125 150
Normal Duty
Rated Output Capacity [kVA] 24 29 36 43 54 65 80 103 124 149
Applicable Motor Output [690V, kW] 15 18.5 22 30 37 45 55 75 90 110
Applicable Motor Output [690V, HP] 20 25 30 40 50 60 75 100 125 150
Applicable Motor Output [575V, HP] 15 20 25 30 40 50 60 75 100 125
Rated Output Current [A] 20 24 30 36 45 54 67 86 104 125
Heavy Duty
Rated Output Capacity [kVA] 17 24 29 36 43 54 65 80 103 124
Applicable Motor Output [690V, kW] 11 15 18.5 22 30 37 45 55 75 90
Applicable Motor Output [690V, HP] 15 20 25 30 40 50 60 75 100 125
Applicable Motor Output [575V, HP] 10 15 20 25 30 40 50 60 75 100
Rated Output Current [A] 14 20 24 30 36 45 54 67 86 104
Carrier Frequency [kHz] 2~9 (Default: 4)
Input Rating
Input Current [A]
Light Duty 29 36 43 54 65 81 84 102 122 147
Normal Duty 24 29 36 43 54 65 66 84 102 122
Heavy Duty 20 24 29 36 43 54 53 66 84 102
Rated Voltage / Frequency 3-phase AC 525 V~ 690 V ( -15%~+10%), 50/60 Hz
Operating Voltage Range 446 ~ 759 V
AC
Frequency Tolerance 47~63Hz
Efficiency [%] 97
Power Factor >0.98
Drive Weight [Kg] 10 ± 1.5 39 ± 1.5 61 ± 1.5
Cooling Method Fan cooling
Braking Chopper Frame C: Built-in Frame D~E: Optional
DC choke Frame C: Optional Frame D~E: Built-in
EMC Filter Frame C~E: Optional
Table 9-5
NOTE
* Parameter 00-16; available load modes: Light Duty (LD), Normal Duty (ND) and Heavy Duty (HD); default setting is LD mode