EasyManua.ls Logo

Delta C2000 Series - Page 341

Delta C2000 Series
936 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 11 Summary of Parameter SettingsC2000
11-6
Pr. Parameter Name Setting Range Default
00-19 PLC command mask
bit0: Control command by PLC force control
bit1: Frequency command by PLC force control
bit2: Position command by PLC force control
bit3: Torque command by PLC force control
Read
only
00-20
Master frequency command
(AUTO) source / Source selection
of the PID target
0: Digital keypad
1: RS-485 communication
2: External analog input (Pr. 03-00)
3: External UP / DOWN terminal (multi-function
input terminal)
4: Pulse input without direction command (Pr.10-16
without direction), use with PG card
5: Pulse input with direction command (Pr. 10-16),
use with PG card
6: CANopen communication card
8: Communication card (does not include CANopen
card)
0
00-21
Operation command (AUTO)
source
0: Digital keypad
1: External terminals.
2: RS-485 communication.
3: CANopen communication card
5: Communication card (does not include CANopen
card)
0
00-22 Stop method
0: Ramp to stop
1: Coast to stop
0
00-23 Control of motor direction
0: Enable forward / reverse
1: Disable reverse
2: Disable forward
0
00-24
Digital keypad frequency command
memory
Read only
Read
only
00-25 User defined characteristics
bit0–3: user defined decimal place
0000b: no decimal place
0001b: one decimal place
0010b: two decimal places
0011b: three decimal places
bit4–15: user defined unit
000xh: Hz
001xh: rpm
002xh: %
003xh: kg
004xh: m/s
0

Table of Contents