Chapter 11 Summary of Parameter SettingsC2000
11-8
Pr. Parameter Name Setting Range Default
00-27 User-defined value Read only
Read
Only
00-29 LOCAL / REMOTE mode
0: Standard HOA function
1: When switching between local and remote, the
drive stops.
2: When switching between local and remote, the
drive runs with REMOTE settings for frequency
and operation status.
3: When switching between local and remote, the
drive runs with LOCAL settings for frequency and
operation status.
4: When switching between local and remote, the
drive runs with LOCAL settings when switched to
Local and runs with REMOTE settings when
switched to Remote for frequency and operation
status.
0
00-30
Master frequency command
(HAND) source
0: Digital keypad
1: RS-485 communication
2: External analog input (Pr. 03-00)
3: External UP / DOWN terminal
4: Pulse input without direction command
(Pr. 10-16 without direction)
5: Pulse input with direction command (Pr. 10-16)
6: CANopen communication card
8: Communication card (does not include CANopen
card)
0
00-31
Operation command (HAND)
source
0: Digital keypad
1: External terminals.
2: RS-485 communication.
3: CANopen communication card
5: Communication card (does not include CANopen
card)
0
00-32 Digital keypad STOP function
0: Disable STOP key
1: Enable STOP key
0
00-40 Homing mode
0000h
X
Note: Forward run = clockwise (CW)
Reverse run = counterclockwise (CCW)