Chapter 12 Description of Parameter SettingsC2000
12.1-00-2
575V Series
Frame A B
kW 1.5 2.2 3.7 5.5 7.5 11 15
HP 2 3 5 7.5 10 15 20
Identity code 505 506 507 508 509 510 511
Rated current for
heavy load (A)
2.1 3 4.6 6.9 8.3 13 16.8
Rated current for
normal load (A)
2.5 3.6 5.5 8.2 10 15.5 20
690V Series
Frame C D E F
kW 18.5 22 30 37 45 55 75 90 110 132 160 200
HP 25 30 40 50 60 75 100 125 150 175 215 270
Identity code 612 613 614 615 616 617 618 619 620 621 622 686
Rated current for
heavy load (A)
14 20 24 30 36 45 54 67 86 104 125 150
Rated current for
normal load (A)
20 24 30 36 45 54 67 86 104 125 150 180
Frame G H
kW 250 315 400 450 560 630
HP 335 425 530 600 745 840
Identity code 687 626 628 629 631 632
Rated current for
heavy load (A)
180 220 290 310 420 675
Rated current for
normal load (A)
220 290 350 385 465 675
Parameter Reset
Default: 0
Settings 0: No Function
1: Write protection for parameters
5: Reset kWh display to 0
6: Reset PLC (including CANopen Master Index)
7: Reset CANopen Index (Slave)
9: Reset all parameters to defaults with base frequency at 50 Hz
10: Reset all parameters to defaults with base frequency at 60Hz
When set to 1, all parameters are read only except Pr. 00-02, Pr. 00-07 and Pr. 00-08. Set Pr.
00-02 to 0 before changing other parameter settings.
When set to 9 or 10, reset all parameters to defaults. If there is a password set in Pr. 00-08,
enter the password set in Pr. 00-07 to reset to default.
When set to 5, kWh displayed value can be reset to 0 even when the drive is operating. Pr.
05-26, Pr. 05-27, Pr. 05-28, Pr. 05-29, and Pr. 05-30 are reset to 0.
When set to 6, clear internal PLC program (includes the related settings of PLC internal
CANopen master)
When set to 7, reset the related settings of CANopen slave.
When set to 6, 7, 9, 10, reboot the motor drive after setting.