EasyManua.ls Logo

Delta C2000 Series - Page 444

Delta C2000 Series
936 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12 Description of Parameter SettingsC2000
12.1-02-19
DO
Terminal Pr. Setting Indexes of MODBUS direct control
RY1 Pr. 02-13 = 51 The bit0 of 2640h
RY2 Pr. 02-14 = 51 The bit1 of 2640h
MO1 Pr. 02-16 = 51 The bit3 of 2640h
MO2 Pr. 02-17 = 51 The bit4 of 2640h
MO10 Pr. 02-36 = 51 The bit5 of 2640h
MO11 Pr. 02-37 = 51 The bit6 of 2640h
MO12 Pr. 02-38 = 51 The bit7 of 2640h
MO13 Pr. 02-39 = 51 The bit8 of 2640h
MO14 Pr. 02-40 = 51 The bit9 of 2640h
MO15 Pr. 02-41 = 51 The bit10 of 2640h
AO
Terminal Pr. Setting Indexes of MODBUS direct control
AFM1 Pr. 03-20=21 The value of 26A0h
AFM2 Pr. 03-23=21 The value of 26A1h
AFM10 Pr. 14-12=21 The value of 26AAh
AFM11 Pr. 14-13=21 The value of 26ABh
Multi-function Output Setting
Default Setting: 0000h
Settings 0000h~FFFFh (0: N.O. ; 1:N.C.)
This parameter is in hexadecimal.
This parameter is set by a bit. If a bit is 1, the corresponding multi-function output acts in an
opposite way.
Example:
If Pr. 02-13=1 and Pr. 02-18=0, Relay 1 is ON when the drive runs and is open when the drive is
stopped.
If Pr. 02-13=1 and Pr. 02-18=1, Relay 1 is open when the drive runs and is closed when the drive
is stopped.
bit setting
bit15 bit14 bit13 bit12 bit11 bit10 bit9 bit8 bit7 bit6 bit5 bit4 bit3 bit2 bit1 bit0
MO20 MO19 MO18 MO17 MO16 MO15 MO14 MO13 MO12 MO11 MO10 MO2 MO1 Reserved RY2 RY1
Terminal Counting Value Reached (returns to 0)
Default Setting: 0
Settings 0~65500
The counter trigger can be set by the multi-function terminal MI6 (set Pr. 02-06 to 23). Upon
completion of counting, the specified multi-function output terminal will be activated (Pr. 02-13, Pr.
02-14, Pr. 02-36, Pr. 02-37 is set to 18). Pr. 02-19 cannot be set to 0.
When the display shows c5555, the drive has counted 5,555 times. If display shows c5555, it
means that real counter value is between 55,550 to 55,559.

Table of Contents