Chapter 12 Description of Parameter SettingsC2000
12.1-02-18
Settings Functions Descriptions
Pr.03-45: The high level for the analog input, default is 50%.
Pr.03-46: The low level for the analog input, default is 10%.
If analog input > Pr.03-45, the multi-function output terminal
operates. If analog input < 03-46, the multi-function output
terminal stops output.
70
Fan warning detection
output
The terminal works when the internal fan warning activates
Example: Crane Application
It is recommended to be used with Dwell function as shown in the following:
For crane application, when the MO is set to 42, the setting of Pr. 02-34 must be greater than Pr.
02-58; Pr. 02-33 must be greater than Pr. 02-57.
To directly control drive’s AO/DO and read current AI/DI status via the standard MODBUS, by
adding the Remote IO function, the corresponding index of 26xx is as following:
bit15 bit14 bit13 bit12 bit11 bit10 bit9 bit8 bit7
bit6 bit5 bit4 bit3 bit2 bit1 bit0
2600h MI15 MI14 MI13 MI12 MI11 MI10 MI8 MI7 MI6
MI5 MI4 MI3 MI2 MI1 REV FWD
2640h - - - - - MO15 MO14 MO13 MO12
MO11 MO10 MO2 MO1 - RY2 RY1
2660h AVI
- - - - - - - - - - - - - -
2661h ACI
- - - - - - - - - - - - - -
2662h AUI
- - - - - - - - - - - - - -
266Ah AI10
- - - - - - - - - - - - - -
266Bh AI11
- - - - - - - - - - - - - -
26A0h AFM1
- - - - - - - - - - - - -
26A1h AFM2
- - - - - - - - - - - - -
26AAh AO10
- - - - - - - - - - - - -
26ABh AO11
- - - - - - - - - - - - -
In addition, the AI and DI value can be read directly, while DO and AO must select MODBUS
control under the corresponding parameter function. The related parameter definition is as
following: