Chapter 12 Description of Parameter SettingsC2000
12.1-02-17
Settings Functions Descriptions
51
Analog output control for
RS-485 (InnerCOM /
MODBUS)
For RS-485 interface (InnerCOM/ MODBUS) output.
Physical
terminal
Setting of
related
parameters
Attribute
Corresponding
Index
RY1 Pr. 02-13 = 51 RW bit0 at 2640H
RY2 Pr. 02-14 = 51 RW bit1 at 2640H
MO1 Pr. 02-16 = 51 RW bit3 at 2640H
MO2 Pr. 02-17 = 51 RW bit4 at 2640H
MO10 or
RA10
Pr. 02-36 = 51 RW
bit5 at 2640H
MO11 or
RA11
Pr. 02-37 = 51 RW
bit6 at 2640H
RA12 Pr. 02-38 = 51 RW bit7 at 2640H
RA13 Pr. 02-39 = 51 RW bit8 at 2640H
RA14 Pr. 02-40 = 51 RW bit9 at 2640H
RA15 Pr. 02-41 = 51 RW bit10 at 2640H
52
Output control for
communication cards
For communication output of communication cards
(CMC-MOD01, CMC-EIP01, CMC-PN01 and CMC-DN01)
Physical
terminal
Setting of
related
parameters
Attribute
Corresponding
Address
RY1 Pr. 02-13 = 52 RW The bit0 of 2640H
RY2 Pr. 02-14 = 52 RW The bit1 of 2640H
MO1 Pr. 02-16 = 52 RW The bit3 of 2640H
MO2 Pr. 02-17 = 52 RW The bit4 of 2640H
MO10 or
RA10
Pr. 02-36 = 51 RW The bit5 of 2640H
MO11 or
RA11
Pr. 02-37 = 51 RW The bit6 of 2640H
RA12
Pr. 02-38 = 51 RW The bit7 of 2640H
RA13
Pr. 02-39 = 51 RW The bit8 of 2640H
RA14
Pr. 02-40 = 51 RW The bit9 of 2640H
RA15
Pr. 02-41= 51 RW The bit10 of 2640H
65
Output for CANopen and
RS-485
To control output of CANopen & RS-485.
66 SO output logic A
Status of drive
Status of safety output
N.O. (MOx=66) N.C. (MOx=68)
Normal
Broken circuit
(Open)
Short circuit
(Close)
STO
Short circuit
(Close)
Broken circuit
(Open)
STL1~STL3
Short circuit
(Close)
Broken circuit
(Open)
68 SO output logic B
67
Analog input signal level
reached
The multi-function output terminals operate when the analog input
level is between the high level and the low level.
Pr.03-44: Select one of the analog input channels (AVI, ACI) to be
compared.