Chapter 12 Description of Parameter SettingsC2000
12.1-02-23
Motor Zero-speed Level
Default: 0
Settings 0~65535 rpm
This parameter should be used with the multi-function output terminals (set to 43). It needs to be
used with PG card and motor with encoder feedback.
Use this parameter to set the level of motor at zero-speed. When the speed is lower than this
setting, the corresponding multi-function output terminal that is set to 43 is ON, as shown below:
Maximum Frequency of Resolution Switch
Default: 60.00
Settings 0.00~599.00Hz
Switch delay time of Maximum output frequency
Default: 0.000
Settings 0~65.000 sec.
Use to improve unstable speed or unstable position due to insufficient analog resolution. Use with
the external terminal (setting to 43). After setting this parameter, you also need to adjust the
analog output resolution of the controller so as to work with the parameter function.

Table of Contents

Other manuals for Delta C2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Series and is the answer not in the manual?

Delta C2000 Series Specifications

General IconGeneral
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Overload Capacity150% of rated current for 60 seconds
CommunicationDeviceNet
ProtectionOvervoltage, Undervoltage, Overcurrent, Overload, Overheat
Humidity5% to 95% (non-condensing)
CoolingForced air cooling
Control ModeV/F Control, Sensorless Vector Control