Chapter 12 Description of Parameter SettingsC2000
12.1-02-28
When Pr. 02-57 = 0, the output current is lower than the setting of Pr. 02-33 Pivot Point of the
current (< Pr. 02-33) or when output frequency is lower than the setting of Pr. 02-58(< Pr. 02-58),
disable the setting of #42 of the multi-function output Pr. 02-13, Pr. 02-14, Pr. 02-16 and Pr.
02-17.
For crane application, when MOx=42, the setting of Pr. 02-34 must be greater than Pr. 02-58;
and Pr. 02-33 must be greater than Pr. 02-57.
Frequency Reached Detection Amplitude
Default: 0.00
Settings 0.00~599.00Hz
IO Card Type
Default: Read only
Settings Read only
1: EMC-BPS01 Card
4: EMC-D611A Card
5: EMC-D42A Card
6: EMC-R6AA Card
11: EMC-A22A
DFM Output Selection
Default: 0
Settings 0: Use frequency with speed control as DFM output frequency
1: Use frequency with system accel./decel. as DFM output frequency
Internal/External Multi-function Input Terminals Selection
Default: 0000h
Settings 0000~FFFFh
This parameter is used to select the terminals MI1~MI15 to be internal terminal or external
terminal. When the MIx has set as internal terminal, then the corresponding external terminal
function will be disabled.
To activate internal terminals via Pr. 02-75 setting.
The setting method is to convert binary number to hexadecimal number for input.

Table of Contents

Other manuals for Delta C2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Series and is the answer not in the manual?

Delta C2000 Series Specifications

General IconGeneral
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Overload Capacity150% of rated current for 60 seconds
CommunicationDeviceNet
ProtectionOvervoltage, Undervoltage, Overcurrent, Overload, Overheat
Humidity5% to 95% (non-condensing)
CoolingForced air cooling
Control ModeV/F Control, Sensorless Vector Control