Chapter 12 Description of Parameter SettingsC2000
12.1-02-29
For example: if setting MI1, MI3, MI4 to be internal terminals, the setting value should be
bit5x2
5
+bit4x2
4
+bit2x2
2
= 1X2
5
+1X2
4
+1X2
2
= 32+16+4=52 as shown in the following. The 522=32h,
Pr. 02-74=34h.
Internal Multi-function Output Terminal Selection
Default: 0000h
Settings 0000~FFFFh
This parameter is used to set the internal terminal action via keypad, communication or PLC.
For example, if setting MI1, MI3 and MI4 to be ON, Pr.02-75 should be set to
bit5X2
5
+bit4X2
4
+bit2X2
2
= 1X2
5
+1X2
4
+1X2
2
= 32+16+4=522 =34h as shown in the following.
The Local/Remote of Digital operation panel has the lowest priority.
When the built-in PLC has use a MIx, the original function of this MIx can still be triggered via
virtual terminal.
Pr. 02-74 and Pr. 02-75 can both do running change.
Pr. 02-74 and Pr. 02-75 setting value are both memorized before power off.
The virtual terminal trigger can still be selected by the setting of Pr. 02-12 Digital Input Operation
Setting (Pr. 02-12=0 N.O. or Pr. 02-12=1 N.C.)