Chapter 12 Description of Parameter SettingsC2000
12.1-06-16
Torque Command at Malfunction
Default: Read only
Settings -32767–32767%
When a malfunction occurs, check the current torque command. If it happens again, it overwrites
the previous record.
Status of the Multi-function Input Terminal at Malfunction
Default: Read only
Settings 0000h–FFFFh
Status of the Multi-function Output Terminal at Malfunction
Default: Read only
Settings 0000h–FFFFh
When a malfunction occurs, check the status of multi-function input / output terminals. If it
happens again, it overwrites the previous record.
Drive Status at Malfunction
Default: Read only
Settings 0000h–FFFFh
When a malfunction occurs, check the current drive status (communication address 2101H). If it
happens again, it overwrites the previous record.
STO Latch Selection
Default: 0
Settings 0: STO latch
1: STO no latch
Pr. 06-44 = 0: STO Alarm Latch. After you clear the cause of the STO Alarm, use a Reset
command to clear the STO Alarm.
Pr. 06-44 = 1: STO Alarm no Latch. After you clear the cause of the STO Alarm, the STO Alarm
clears automatically.
All of STL1–STL3 errors are “Alarm Latch” mode (in STL1–STL3 mode, the Pr. 06-44 function is
no effective).
Treatment to Output Phase Loss Protection (OPHL)
Default: 3
Settings 0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
The OPHL protect function is active when the setting is not 3.
Detection Time of Output Phase Loss
Default: 3.000
Settings 0.000–65.535 sec.