7
VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
7-5
Code Displayed Error Explanations Treatments
R1 setting error
îš‹
Re-do the setting or execute the
Tuning function
Fan fault
îš‹
Check whether the fan is blocked
îš‹
Return to the factory
Power input phase-lacking
Phase-lacking within the
input power of the AC drive
Three imbalanced
conditions existed within
the input voltage
îš‹
Check whether the power voltage
is normal
îš‹
Check whether the screw at the
input power terminal is tightened
Other faults
îš‹
Reserved
The motor parameter
-Tuning- failed
îš‹
Re-check the wiring and reset the
parameter
Communication error
îš‹
Check whether the communication
signal is counter-connected (RJ11)
îš‹
Check whether the communication
form is correct
Upper and lower legs of
PWM are of the same LOW
level
îš‹
Return to the factory
KEYPAD communication
overtime
îš‹
Check whether the communication
circuit is well-conducted
RS485 communication
overtime
îš‹
Check whether the communication
circuit is well-conducted