VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-16
01-00
Maximum
Operation Frequency
Set Point of
the Operation
Frequency
Time
01-12 01-14
01-16 01-18
01-20
01-13 01-15
01-16
01-19
01-21
Definition of the Acceleration/Deceleration Time
01-22 JOG Frequency
a
Factory setting 6.00
Settings 0.00Hz~400.00Hz
This parameter determines the Jog frequency. The Jog function may be selected by
the JOG key on the PU05 keypad or the external I/O terminals. When the drive is
operating under a RUN command, the JOG operation is disabled. Likewise, the drive
will not accept a RUN command while the JOG command is enabled.
01-23 1
st
/4
th
Acceleration/Deceleration Frequency
a
Factory setting 0.00
Settings 0.00Hz~400.00Hz
This parameter selects the frequency point for transition from acceleration/deceleration
time 1 to acceleration/deceleration time 4.
The transition from acceleration/deceleration time 1 to acceleration/deceleration time 4,
may also be enabled by the external terminals (Pr. 02-01 to 02-06). The external
terminal has priority over Pr. 01-23.