Pr3
Password 0 999
Display read-out
Param
eter
Description min max M. u. Resolu
tion
dP 1
Default read-out of the top display 0 15
dP 2
Default read-out of the bottom display 0 18
dP 3
Default display read-out configuration top / bottom
0= Configurable (parameters dP1 and dP2)
1= Top display: Evaporator IN, Bottom display: Evaporator OUT
2= Top display: Condenser IN, Bottom display: Condenser OUT
3=Top display: temperature/Condensing pressure, Bottom Display:
evaporating pressure
0 3
dP 4
Display visualization in stand by mode
0= the display visualizes “Stby”
1= the display visualizes what defined by parameters dP1 and dP2
2= the display visualizes “OFF”
0 2
Display read-out of the remote keyboards
dP 5
Display default read-out of the remote keyboard 1
0= the read-out depends on the paremeters dP01 – dP02 – dP03
1= the read-out shows the NTC probe of the remote panel
0 1
dP 6
Display default read-out of the remote keyboard 2
0= the read-out depends on the paremeters dP01 – dP02 – dP03
1= the read-out shows the NTC probe of the remote panel.
0 1
dP 7
Display visualization of the remote keyboard 1 in stand by mode
0= the display visualizes “Stby”
1= the display visualizes what defined by parameters dP1 and dP2
2= the display visualizes “OFF”
0 2
dP 8
Display visualization of the remote keyboard 2 in stand by mode
0= the display visualizes “Stby”
1= the display visualizes what defined by parameters dP1 and dP2
2= the display visualizes “OFF”
0 2
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Configuration
Param
eter
Description min max M. u. Resolu
tion
Unit Model
CF 1
Type of unit
0= Air / air Chiller
1= Air / water Chiller
2= Water / water Chiller
0 2
CF 2
Selection type rof unit
1= only chiller
2= only heat pump
3= chiller and heat pump
0 3
CF 3
Motocondensing unit
0= no
1= si
0 1
Compressors
CF 4
Number of compressors circuit 1
1= 1
2= 2
1 2
CF 5
Number of compressors circuit 2
0= 0
1= 1
0 1