1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Defrost
Param
eter
Description min max udm Risolu
zione
dF 1
Defrost configuration:
0= Not enabled
1= Temperature / pressure
2= start depends on par. dF24 stop for time duration
3= start depends on par. dF24 stop for external contact
4= defrost with condenser fan
0 4
dF 2
Temperature or pressure of the defrost start-up
-50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
bar
psi
Dec
int
Dec
Int
dF 3
Temperature or pressure of the defrost stop -50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
bar
psi
Dec
int
Dec
Int
dF 4
Minimum defrost duration 0 250 Sec
dF 5
Maximum defrost duration 1 250 Min
dF 6
Time delay between the defrost of two circuits 0 250 Min
dF 7
OFF compressor delay before the defrost 0 250 Sec
dF 8
OFF compressor delay after the defrost 0 250 Sec
dF 9
Defrost interval time of the same circuit 1 99 Min
dF 10
Temperature setpoint for combined defrost of the 1
st
circuit after
parameter DF10 counting
-50.0
-58
70.0
158
°C
°F
Dec
int
dF 11
Temperature setpoint for combined defrost end of the 1
st
circuit. -50.0
-58
70.0
158
°C
°F
Dec
int
dF 12
Temperature setpoint for combined defrost of the 2
nd
circuit after
parameter DF10 counting
-50.0
-58
70.0
158
°C
°F
Dec
int
dF 13
Temperature setpoint for combined defrost end of the 2
nd
circuit -50.0
-58
70.0
158
°C
°F
Dec
int
dF 14
Activation of all the steps of the 1
st
circuit during the defrost
0= Not enabled
1= Enabled
0 1
dF 15
Activation of all the steps of the 2
nd
circuit during the defrost
0= Not enabled
1= Enabled
0 1
dF 16
Delay between two compressor activation in defrost (compressors of
the same circuit)
0 250 Sec
dF 17
Fan control during defrost / dripping time
0= Not enabled
1= Only in defrost
2= For both functions defrost / dripping time
0 2
dF 18
Pressure / temperature setpoint to force the ventilation ON during the
defrost.
-50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
bar
psi
Dec
int
Dec
Int
Forced defrost
dF 19
Minimum time delay before a forced defrost 0 250 sec
dF 20
Pressure / temperature setpoint for a forced defrost -50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the dixell IC200CX Series and is the answer not in the manual?

dixell IC200CX Series Specifications

General IconGeneral
Branddixell
ModelIC200CX Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals