1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
dF 21
Forced defrost differential 0.1
1
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
Defrost operative mode
dF 22
Defrost start-up in unit with 2 circuits
0= Independent
1= If both have reached the necessary requirements
2= If one has reached the necessary requirements
0 2
dF 23
End defrost in unit with 2 circuits and common ventilation
0= Independent
1= If both have reached the necessary end defrost requirements
2= If one has reached the necessary end defrost requirements
0 2
Start / stop defrost from analog input
Param
eters
description min max udm resolut
ion
dF 24
Start / stop defrost probe
0= start and stop with condenser temperature / pressure probe
1= start with evaporator pressure probe / stop with condenser
temperature / pressure probe
2= start with condenser temperature / pressure probe / stop with
evaporator pressure probe
3= start and stop with evaporator pressure probe
0 3
Supply fan functioning during defrost cycle
dF 25
Set point to enable defrost with condenser fan
-50.0
-58
70.0
158
°C
°F
Dec
int
Defrost with condenser fan
dF 26
Supply fan status during the defrost cycle
0= Enabled
1= Not enabled
0 1
Minimum temperature water outlet during defrost
dF 27
Probe selection for minimum temperature outlet during defrost 0 6
dF 28
Set point for minimum temperature outlet during defrost
-50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int
Pr1
Password 0 999
Pr2
Password 0 999
Pr3
Password 0 999
Alarms
Param
eters
Description min max m. u. Resolu
tion
Low alarm
AL 1
Low pressure alarm delay from analog and digital input 0 250 Sec
AL 2
Low pressure alarm delay if the low pressure switch is used for the
pump down.
AL02= 0 low pressure alarm not enable during compressor switching
off from pump down and if compressor OFF
AL02 0 low pressure alarm enable after AL02 (starting from
compressor switch off) time with compressor OFF
0 250 Sec 10 Sec
AL 3
Low pressure alarm setpoint from analogue input -50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the dixell IC200CX Series and is the answer not in the manual?

dixell IC200CX Series Specifications

General IconGeneral
Branddixell
ModelIC200CX Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals