• signal cable AWG 24
• power supply cable AWG 22
• relay output AWG 17
General notes:
• Check the connecitons and the line voltage before turning on the power supply.
• Keep low voltage cables, such as analogue/digital inputs/outputs and probes, away from power
cables and terminals.
• Respect the maximum load current of each relay output, in case of power loads use filtered
contactors.
18 TECHNICAL DATA
Housing: self extinguishing ABS.
Case: frontal 32x74 mm; depth 60mm
Mounting: panel mounting in a 29x71mm panel cut-out
Frontal protection: IP65
Display:
Top Display 4 digits with d.p.
Bottom Display 4 digits with d.p.
Power supply:
12Vac -10%÷+15% or
24 Vac/dc ±10% 50/60 Hz
Power absorption: 10VA max.
Analog Inputs: 4 configurable (NTC/PTC/dig. input) + 2 configurable (NTC/PTC/4÷20ma/0÷5Volt/dig.
input)
Digital inputs: # 11 (free voltage)
Relay outputs: IC206CX: 6 SPDT 5(2) A, 250Vac, IC208CX: 8 SPDT 5(2) A, 250Vac
Max. current on common line: 10A
Data storing: on the non-volatile memory (EEPROM).
Operating temperature: 0÷55 °C.
Storage temperature: -30÷85 °C.
Relative humidity: 20÷85% (no condensing)
Measuring range: - 50÷110 °C (- 58 ÷ 230 °F) NTC / -50.0÷150 °C (-58÷302 °F) PTC or 0÷ 50 bar
(0÷725 psi)
Resolution: 0,1 °C or 1 °F
Accuracy of the controller at 25°C: ±0,7 °C ±1 digit