1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
8 ANALOG AND DIGITAL OUTPUT CONFIGURATION
8.1 ANALOG INPUT PB1 - PB2 PB5 PB6
Parameters involved:
CF08 = Configuration PB1
CF09 = Configuration PB2
CF12 = Configuration PB5
CF13 = Configuration PB6
0. Not enabled
1. Temperature probe PTC for compressor #1 discharge
2. Temperature probe NTC for evaporator inlet
3. Temperature probe NTC for evaporator #1 outlet
4. Temperature probe NTC for evaporator #2 outlet
5. Temperature probe NTC for common evaporator outlet
6. Temperature probe NTC for common hot water condenser inlet
7. Temperature probe NTC for hot water of the condenser circuit #1 inlet
8. Temperature probe NTC for hot water of the condenser circuit #2 inlet
9. Temperature probe NTC for hot water of the condenser circuit #1 outlet
10. Temperature probe NTC for hot water of the condenser circuit #2 outlet
11. Temperature probe NTC for hot water of the condenser common outlet
12. Temperature probe NTC (external temperature) for dynamic setpoint / boiler / change over
13. Temperature probe NTC for combined defrost circuit #1
14. Temperature probe NTC for combined defrost circuit #2
15. Temperature probe NTC for auxiliary output #1
16. Temperature probe NTC for auxiliary output #2
17. Temperature probe NTC for condensing circuit #1
18. Temperature probe NTC for condensing circuit #2
Every analogue input can be configured as digital input; after the number 18, the values o 1 c38
allow the configuration of the analogue input as digital inputs with the same meaning (o 1= remote
ON/OFF, o 2= Remote chiller / heat pump, …..).
8.2 ANALOG INPUT CONFIGURATION PB3 - PB4
Parameter involved:
CF10 = Configuration PB3
CF11 = Configuration PB4
0 Not enabled
1 Temperature probe PTC for compressor #1 discharge
2 Temperature probe NTC for evaporator inlet
3 Temperature probe NTC for evaporator #1 outlet
4 Temperature probe NTC for evaporator #2 outlet
5 Temperature probe NTC for common evaporator outlet
6 Temperature probe NTC for common hot water condenser inlet
7 Temperature probe NTC for hot water of the condenser circuit #1 inlet
8 Temperature probe NTC for hot water of the condenser circuit #2 inlet
9 Temperature probe NTC for hot water of the condenser circuit #1 outlet
10 Temperature probe NTC for hot water of the condenser circuit #2 outlet
11 Temperature probe NTC for hot water of the condenser common outlet